Descargar Imprimir esta página

Function; Display Elements; Part Label - Balluff BTL BNC 00 Serie Manual De Instrucciones

Ocultar thumbs Ver también para BTL BNC 00 Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 93
BTL BNC_ 00- _ _ _ _ -C15A _ _ _0- _ _ _ _ _ _ / BTL ZNC_ 00- _ _ _ _ -C15A _ _ _0- _ _ _ _ _ _
Magnetostrictive Linear Position Sensor – Rod Style
4
Product description (continued)
4.2

Function

To determine the position of a plant component, a magnet
is connected to the component. Together they are moved
along a waveguide located inside the BTL.
An internally generated INIT pulse interacts with the
magnetic field of the magnet to generate a torsional wave
in the waveguide which propagates at ultrasonic velocity.
The component of the torsional wave which arrives at the
end of the waveguide is absorbed in the damping zone to
prevent reflection. The component of the torsional wave
which arrives at the beginning of the waveguide is
converted by a coil into an electrical signal. The position of
the magnet and thus at the same time that of the plant
component is determined from the running time of the
shaft.
Depending on the version, 1 or 2 outputs are available and
the position is output as a voltage or current value with
rising or falling gradient.
Up to 2 magnets can be used for FMM (Flexible Magnet
Mode).
The following functions can be selected for the output
values:
Position
Velocity
Position difference
The entire range of functions can only be
configured with the PC software B
E
T
(BET). For this, the IO-Link
nginEEring
ool
master must be connected. Communication is
realized via IO-Link.
www.balluff.com
4.3
Signal
Green
Yellow flas-
hing, 3 Hz
Red flashing,
1 Hz
Red flashing,
3 Hz
1)
Is only displayed for versions with 2 current outputs if the error is
present at the same time at both outputs.
Tab. 4-1:
With 1 magnet and 2 outputs the priority of the LED
display is as follows (highest to lowest priority):
Output error
Measurement error
Warning
Normal function
For FMM (Flexible Magnet Mode) with 1 magnet the LED
display relates to output 1 (output 2 issues the error value
continuously).
For FMM (Flexible Magnet Mode) with 2 magnets the LED
alluff
display shows the status with the highest priority of both
outputs.
More than 2 magnets are ignored.
4.4
Order code
2)
Type
3)
Serial number
4)
Fig. 4-2:

Display elements

Meaning
Normal function
Magnet is within the measuring range.
Warning
Magnet is outside the measuring range.
Measurement error
No magnet
Output error
1)
Short-circuit at voltage output or inter-
ruption on current output.
LED display

Part label

2)
4)
Part label (example)
english
3)
4)
9

Publicidad

loading

Este manual también es adecuado para: