down the hidden button, then press and release
the right button.
EVOPLUS circulators offer 2 menus: user menu
and advanced menu. The user menu is
accessible from the Home Page by pressing and
releasing the central "Menu" button.
The user menu is accessible from the Home Page
by holding down the central "Menu" button for 5
seconds.
Page 1.0
The factory settings are set from Page 1.0 by
holding down the left and right buttons at the same
time for 3 seconds.
The resetting of the factory settings will be notified
by the appearance of the symbol
word "Default"
Page 2.0
The regulating mode is set from Page 2.0. You
can choose between the following modes:
1
regulation.
2
regulation with set-point set by external signal (0-
10V or PWM).
3
regulation
temperature.
4
= Regulation with constant differential
pressure.
5
regulation with set-point set by external signal (0-
10V or PWM).
6
regulation
temperature.
ENGLISH
next to the
= Proportional
differential pressure
= Proportional differential pressure
= Proportional differential pressure
with
set-point
depending
on
= Constant differential pressure
= Constant differential pressure
with
set-point
depending
on
21
Page 2.0 displays 3 icons which represent:
- central icon = setting currently selected
- right icon = next setting
- left icon = previous setting
Page 3.0
Page 4.0
Page 5.0
7
= Regulation with constant curve with
rotation speed set from the display.
8
= Regulation with constant curve with
rotation speed set by an external signal (0-10V or
PWM).
The regulating set-point can be modified from
Page 3.0.
Depending on the type of regulation chosen on
the previous page, the set-point to be set will be a
head or, in the case of a Constant Curve, a
percentage of the rotation speed.
On Page 4.0 it is possible to modify the parameter
THs with which to make the curve depending on
temperature (see Par. 8.1.4).
This page will be displayed only for the regulating
modes depending on fluid te mperature.
Page 5.0 allows you to set the "auto" or "economy"
operating mode.
"Auto" mode disables the reading of the status of
digital input IN2 and in fact the system always
activates the set-point set by the user.
"Economy" mode enables the reading of the
status of digital input IN2. When input IN2 is
energised the system activates a percentage