Instale los carteles adjuntos al equipo y especificados en el capítulo 1.3 "Contenido del envío"en un
lugar bien visible carca del equipo.
Pos : 55 /Anl eitungen/Elek tronik/FU und Starter/1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 2_Ergänz ung [SK 1xx E, SK 2xxE, SK 5xx E, -FDS, 5x xP, 3xxP] @ 7\mod_1433943883212_2870.docx @ 223889 @ 5 @ 1
Requisitos UL/CSA según el informe
Pos : 57 /Anl eitungen/Elek tronik/FU und Starter/1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 3_original_W ortlaut [SK 500P] @ 91\mod_1661168466490_0.docx @ 2937965 @ @ 1
Information
•
"Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the Manufacturer Instructions, National Electrical Code and any
additional local codes".
CSA: For Canada: "Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Canadian Electrical Code, Part I".
•
"Use 60 °C Copper Conductors Only", or "Use min. 60°C rated Copper Conductors Only", or equivalent.
Higher temperature ratings are acceptable.
•
For installations according to Canadian National Standard C22.2 No. 274:
"For use in Pollution Degree 2 and Overvoltage Category III environments only", or equivalent.
•
"Maximum surrounding air Temperature 40°C."
•
The devices are not allowed for use in corner grounded supplies, with that the maximum working voltage to
ground is considered to be 240Vac or 277Vac.
Frame
Size
all
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 DC Symmetrical Amperes, 410 Volts
(-123 Devices) or 715 Volts (-340 Devices) Max., When Protected by R/C Semiconductor fuses, type______,
manufactured by _____", as listed in
all
"Suitable For Use On A Circuit Capable Of Delivering Not More Than ______ rms Symmetrical Amperes, 240 (1-
phase) or 480 (3-phase) Volts Max., When Protected by High-Interrupting Capacity, Current Limiting Class
____Fuses or faster, rated ______Amperes, and ____Volts", as listed in
all
"Suitable for Use On A Circuit Capable Of Delivering Not More Than _______ rms Symmetrical Amperes, ____
Volt maximum" (240V for 1-phase models or 480V for 3-phase models),
"When Protected by Circuit Breaker (inverse time trip type) in accordance with UL 489, rated ______ Amperes,
and _______Volts", as listed in
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class RK5 Fuses or faster, rated max. 15 Amperes.
3
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class RK5 Fuses or faster, rated max. 30 Amperes".
4
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting Class J Fuses or
faster, rated max. 125 Amperes".
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 20000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class J Fuses or faster, rated max. 15 Amperes".
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 15 Amperes and respectively 240 or 480 Volts min.".
3
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 30 Amperes and respectively 240 or 480 Volts min.".
4
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in accordance with UL
489, rated max. 125 Amperes and 480 Volts min.".
1
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, DC 715 V max, when Protected by 50 215 26 from SIBA rated max. 20 Amperes"
1)
7.2.1 "Datos eléctricos 3~ 400 V
"
BU 0800 es-4622
description
1)
1)
1 Información general
1)
21