If several auxiliary pressure values are configured at the same time on different inputs, the system indicates Pi when at least one
function is activated. For simultaneous activations, the pressure reached will be the lowest from those with the input active. The alarm
is cleared when no input is activated.
Response of auxiliary pressure function according to setting of INx and input
Parameter
value
INx
3
4
6.6.13.4
Setting the system enable and fault reset
The signal that enables the system can be supplied from any input (for electrical connections, refer to paragraph 2.2.4.2) The system
enable function is obtained by setting the parameter INx, associated with the input where the enable signal is connected, to one of the
values in Table 24.
When this function is active, the system is totally disabled, and F3 is displayed n the STATUS line of the main page.
When several system disable functions are configured at the same time on different inputs, the system indicates F3 when at least one
function is activated and clears the alarm when none are activated.
The input must be active for at least 1 second for the system to implement the disable function.
When the system is disabled, the input must not be active for at least 1 second for the function to be deactivated (system re-enable).
The function behaviour is summarised in Table 25.
If several disable functions are configured at the same time on different inputs, the system indicates F3 when at least one function is
activated. The alarm is cleared when no input is activated.
Response of system enable and fault reset function according to setting of INx and input
Parameter
value
INx
5
6
7
8
9
14*
15*
* Function available for firmware V 26.1.0 and later versions
Input
configuration
Active with high signal
on input (NO)
Active with low signal
on input (NO)
Table 26: Auxiliary setpoints
Input
configuration
Active with high signal
on input (NO)
Active with low signal
on input (NO)
Active with high signal
on input (NO)
Active with low signal
on input (NO)
Active with high signal
on input (NO)
Active with high signal
on input (NO)
Active with low signal
on input (NC)
Table 27: System enable and fault reset
ENGLISH
Input status
Auxiliary set point of same
Absent
name not active
Auxiliary set point of same
Present
Auxiliary set point of same
Absent
Auxiliary set point of same
Present
name not active
Input status
Absent
Inverter Enabled
Present
Inverter Disabled
Absent
Inverter Disabled
Present
Inverter Enabled
Absent
Inverter Enabled
Inverter disabled + block
Present
Inverter disabled + block
Absent
Present
Inverter Enabled
Absent
Inverter Enabled
Present
Absent
Inverter Enabled
Inverter Disabled no error
Present
Absent
Inverter Disabled no error
Present
Inverter Enabled
115
Operation
name active
name active
Operation
reset
reset
Block reset
message
message
Display
None
Px
Px
None
Display
None
F3
F3
None
None
F3
F3
None
None
None
F3
F3
None