4180-4350
Note: The space above the unit must be free from obstacles. The installation must comply with the requirements of the EN 378 standard.
If more than one unit is installed, the minimum distance between the finned coils should be at least 2 m.
(*)
(**) Minimum distance for the removal of the pump unit and the relative tank. If the accessory is not present, the distance can be reduced.
(***) Minimum distance for the electrical panel opening.
N.B.
When installing the unit, bear the following in mind:
non-soundproofed reflecting walls near the unit may increase the total sound pressure level reading near the appliance by as much as 3 dB(A) for
every surface;
install suitable anti-vibration mountings under the unit to avoid transmitting vibrations to the building structure;
on top of buildings, solid floor frames can be provided which support the unit and transmit its weight to the support elements of the building;
make all water connections using elastic joints; pipes must be firmly supported by solid structures. If the pipes are routed through walls or panels, insu-
late with elastic sleeves.
If, after installation and start-up of the unit, structural vibrations are observed in the building which provoke such strong resonance that noise is generated
in other parts of the building, refer to a qualified acoustic technician for a complete analysis of the problem.
2.4.6. DISTRIBUTION OF THE WEIGHTS
EQRU-EQRUSS
Weight
(*)
Kg
Support
Kg
A
Kg
B
Kg
C
Kg
D
IOM_EQRU-SS_EQRHU-SS_2160a4350_208676_230601_ES-EN-FR-DE-IT
81
2160
2180
4180
1405
1405
1790
522
522
626
146
146
269
161
161
269
575
575
626
EQRU-EQRUSS
mm
1500
L1 (*)
mm
1500
L2 (**)
mm
1500
L3 (*)
mm
1000
L4 (***)
4200
4220
4240
1790
1790
1850
624
624
646
271
271
278
271
271
279
624
624
647
EQRU-EQRUSS
EQRHU-EQRHUSS
EQRHU-EQRHUSS
mm
2000
L1 (*)
mm
1500
L2 (**)
mm
2000
L3 (*)
mm
1500
L4 (***)
4280
4330
4350
2270
2370
2370
819
926
926
305
259
259
311
259
259
835
926
926