Hitecsa ADVANCE EQRU-EQRUSS 2160 Manual De Instalación, Uso Y Mantenimiento página 98

Enfriadoras de agua y bombas de calor con condensación de aire y ventiladores helicoidales. serie de compresores herméticos scroll y refrigerante r32

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

DANGER!
Pay attention to high temperatures near the compressor heads and the flow pipes of the cooling circuit.
Control
General cleaning and inspection of the unit
Finned coils
Fans
Compressor: oil check
Exchangers
Water filter
IMPORTANT!
Provide mandatory controls and inspections pursuant to EU 517/2014.
General cleaning and inspection of the unit
Every six months, the unit should be cleaned using a moist cloth. The general conditions of the unit should always be checked every six months. Any
corrosion must be treated with protective paints in order to prevent possible damage.
IMPORTANT!
Provide mandatory controls and inspections pursuant to EU 517/2014.
Cleaning of Finned Coils
DANGER!
Pay attention to the lugs and edges of the battery.
The coils must be washed and brushed gently with water and soap. Remove any foreign bodies from the condensing coils which may block the passage
of air, such as: leaves, paper, debris, and so on; Replace the coils should it not be possible to clean them. Failure to clean the coils increases pressure
drops and therefore reduces overall machine performance. For better battery protection, it is recommended to install the RPE accessories (battery protec-
tion networks) or FMB (metal filters batteries).
IOM_EQRU-SS_EQRHU-SS_2160a4350_208676_230601_ES-EN-FR-DE-IT
98
Frequency
Every 6 months, the unit must undergo general
washing and its status must be checked
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
Every 6 months
At least every 12 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
At least every 6 months.
In the case of installation with harsh operating
conditions, increase the frequency of the control.
EQRU-EQRUSS
EQRHU-EQRHUSS
Notes
Any points where corrosion is starting need to be
touched up with protective paint.
The coils must be kept clear from any obstruc-
tions. If needed, they must be washed with deter-
gents and water. Brush the fins gently to keep
them from being damaged.
The fan grilles must be kept clear from any ob-
structions. Make sure the motors and fan blades
are clean and that there are no abnormal vibra-
tions.
The units are equipped with oil sight glasses on
the compressor. The lubricating oil level in the
compressor can be checked by means of the
sight-glass.
Any incrustation of the exchanger may be de-
tected by measuring the pressure-drop between
the inlet and outlet pipes, using a differential pres-
sure gauge.
It is mandatory to install a mesh filter on the unit's
inlet water piping. This filter must be cleaned from
time to time.