On/Off delay
Timer 1 in
Timer 1 out
T
T = Timer 1 delay
[3] On/Off delay
[4] Pulse
[5] Sym flasher
A.321 Timer 1 set src
Select input signal of Timer 1. See list of I.000
A.322 Timer 1 delay
Set delay of Timer 1. See list of I.000
Example of Timer 1 use:
The default configuration of I.100 "Dig output 1 cfg" is [51] "Contactor".
For the needs of external sequences is necessary to delay of 3 sec the rising edge.
You can get this behaviour with the Timer 1.
The necessary configurations are:
A.320 Timer 1 mode = [1] On delay
A.321 Timer 1 set src = [26] Contactor
A.322 Timer 1 delay = 3.0 sec
I.100 Dig output 1 cfg = [78] Timer 1 out
AGL50-EV
T
T
T
T
The closure of the Input (On) is transferred on Output after pre-set time has elapsed.
The opening of the Input (Off) initiates the pre-set delay, after which the Output is reset (Off).
The closure of the Input (On) is transferred immediately on the Output.
After pre-set time has elapsed, the Output reset (Off).
Symmetrical flasher
Timer 1 in
Timer 1 out
T
T = Timer 1 delay
The closure of the Input (On) is transferred immediately on the Output.
The Output cycle between On and Off for as long as Input is close (On).
The ratio is 1:1 (time On = time Off)
Pulse
Timer 1 in
Timer 1 out
T
T = Timer 1 delay
T
T
T
T
T
T
t<T
t<T
0
3.00
0
27
0.00 30.00
39