HOME STANDBY GENERATOR- ALL aXis CONTROLLER
When this fault occurs, the HSB will light the RED icon, shut down
and re-start will be disabled. The exterior warning LED on the
back of the HSB enclosure will be activated and lit. Check and
adjust AVR. Set Voltage to 240 VAC.
Low Battery
The RED icon will be lit if the battery voltage falls below 21.0
volts for at least 5 seconds while the engine is running. If the
battery voltage rises above 22 volts, the icon will turn off. Battery
voltage is NOT monitored when the engine is cranking, just when
the engine is running. If the RED icon comes on it will not shut
the HSB off, it will remain lit until the battery condition meets the
required output.
When the icon remains lit, the battery charging should be checked
and the condition of the batteries. Follow the FAULT CODE RESET
instructions to clear the fault after service.
Requires Maintenance
The RED icon will be lit if the HSB generator is ready for
maintenance.
The maintenance hour meter counts from 100 hours to 0. You
need to reset when the hour meter reaches 0. Refer to the
scheduled maintenance chart.
Refer to "Resetting the maintenance hour meter" for instructions
after performing maintenance.
fAULT PROTECTION
In all cases when the icon is RED, this is an indicator that the
HSB has registered a fault and must be corrected. Only the "LOW
BATTERY" and "MAINTENANCE" icons will not latch out or shut
down the HSB. ALL other RED icon faults will latch out, shut down,
disable starting and light the RED icon on the aXis Controller and
the exterior warning LED on the backside of the HSB.
MODELS
®
APPROXIMATE ENGINE STARTER CRANk CYCLE TIMES
10 seconds ON
10 seconds OFF
(5 Cycles Total)
If the HSB fails to start, the "OVER CRANK" icon will be lit on the
aXis Controller and the exterior warning LED on the backside of
the HSB.
fAULT CODE RESET
In the event a fault has occurred push OFF button to reset then
AUTO button to re-arm.
All faults should be taken seriously and corrected before reset
process is performed.
Wi-fi Setup Method
1. Use a Wi-Fi enabled device (laptop, smart phone, tablet, etc.)
in near proximity to the ATS.
2. Search and connect to network name (SSID) "Champion
####" where #### will match the last four digits of the serial
number that is printed on the control board.
2a. The password for the network is located on a label on the
dead front of the ATS.
During the setup your device will disconnect from the internet.
The Champion Wi-Fi is a direct connection between your
device (laptop, smart phone, tablet, etc.) and the ATS, and it
does not connect to the internet. Some Android devices may
show the following screen – Choose "Connect only this time."