HOME STANDBY GENERATOR- ALL aXis CONTROLLER
6. Switch Generator circuit breaker to the "ON' position.
7. Replace the deadfront by sliding it from the bottom up
into the cabinet; panel should index into the door latch
protrusions. Secure it to the deadfront bracket with included
nut and stud.
8. Replace the door and secure with included hardware. It is
recommended to secure the door with a lock.
9. Return to HSB and press the controller to the "AUTO"
position. Confirm icons indicate Utility power is active, Utility
side relay is closed, and home is receiving power.
10. Close and lock HSB hoods return keys to customer.
NEMA 1 – This type of enclosed ATS is for indoor installations
only.
NEMA 3R – This type of enclosed ATS is similar to the indoor box,
except that it is a weatherproof enclosure and required for exterior
installations by code. The enclosure only has knockouts on the
bottom side for the enclosure, requires water tight fasteners/
grommets when installed outside per code. This enclosure can
also be used inside.
HSB Test
SPEED SETTING NO LOAD - 14-kW (MODEL 100515)
Do NOT move forward until the HSB generator AC output voltage
and frequency are correct and within the stated limits.
1. If the no-load voltage is correct but no-load frequency is
incorrect, the engine governed speed requires adjustment.
1a. Engine speed is normally set to 3750 RPM (62.5 HZ) high
speed no load (HSNL)
1b. Set engine speed with no electrical load on the generator
1c. Use long needle nose pliers, or a long screw driver, to
bend the spring anchor on the fixed speed controls.
i. To increase engine speed HSNL bend the spring
anchor tang on the fixed speed controls away from the
governor lever to increase spring tension.
MODELS
®
ii. To decrease engine speed HSNL bend the spring
anchor tang on the fixed speed controls toward the
governor lever to decrease spring tension.
SPEED SETTING NO LOAD - 22-kW (MODEL 100304)
No speed adjustments are necessary as it's governed by an
electronic speed controller.
Proceed with caution. Once the Utility Power is turned ON, the
ATS is now electrically hot. The feeder lines and terminals are
now live.
Contact with these connections will result in extremely
hazardous and possibly fatal electrical shock. Use the correct
procedures as described in national electrical codes.
The manufacturer recommends that a licensed electrician or
an individual with complete knowledge of electricity perform
these procedures.
ATS door opened and dead front removed as well as the HSB hood
and electrical access panel removed for the following sections
1. Place aXis Controller in the OFF position and remove aXis
Controller fuse.
2. Turn ON the utility power supply to the ATS.
46
INSTALLATION
DANGER
WARNING