HOME STANDBY GENERATOR- ALL aXis CONTROLLER
ATS and HSB Status Using WIfI
1. Using a WIFI enabled device, connect to the "Champion HSB"
WIFI network following steps 1, 2, and 3 from WIFI Setup
Method.
2. After loading the Home Standby Generator Settings page,
locate and click the
page.
3. You are now viewing the ATS and HSB status page. Items
such as voltage, frequency, current, etc. can all be viewed for
both utility and HSB power. All of the information is live. There
are three tabs located at the top of the page.
ATS, GEN, and LMM. Each tab will display the status for
the Transfer Switch, Home Standby Generator, or Load
Management Module(s) respectively.
4. When finished viewing the status of the ATS, Generator, and
LMM, close your browser and disconnect from the WIFI.
Programming aXis Controller
Setting values are not autosaved. You must press OFF to save
the changes and exit the programming.
Please wait for the decimal point to stop flashing before
moving on to the next function. If you hit
decimal point is still flashing, it does not save the change.
1. To begin programming, disable AUTO by selecting OFF
2. After the HSB is set to OFF, press and hold
changes (decimal point will flash) to enter programming
mode. The display will show YA for year and the clock icon
will illuminate.
Please wait for the decimal point to stop flashing before
moving on to the next function. If you hit
the decimal point is still flashing, it doesn't save the change.
MODELS
®
icon at the bottom right corner of the
®
NOTICE
too soon while the
until the screen
too soon while
3. Year (Y) - choose current year (example 2021 would be 21)
with 18 to 47.
Set year using
for next
4. Month (M) - choose January to December with 1-12.
Set month using
for next
5. Day (D) - choose the day from 1 to 31.
Set day using
for next
6. Week Day - choose week day from 1 to 7.
Set week using
— 1= Monday
— 2= Tuesday
— 3= Wednesday
— 4= Thursday
— 5= Friday
— 6= Saturday
— 7= Sunday
for next
7. Hour (H) - choose hours in military time 0 - 23.
Set hour using
for next
8. Minute (m) - choose the minute from 0-59.
Set minute using
for next
9. Daylight Saving Time (DST) - choose DST on (1) or off (0).
Set DST using
for next
10. Maintenance Hour Meter (H) - Factory setting is 100 hours.
View current hours and reset as needed.
Set maintenance hour meter using
for next
11. Exercise
.
OFF
ARRÊT
Set exercise schedule using
— 0= no exercise
— 1= 1 time per month (12 times annually)
— 2= 2 times per month (24 times annually)
— 3= 4 times per month (48 times annually)
— 4= weekly (52 times annually)
for next
43
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE