Descargar Imprimir esta página

Champion Global Power Equipment 100304 Manual De Instalación página 51

Ocultar thumbs Ver también para 100304:

Publicidad

Idiomas disponibles

Idiomas disponibles

HOME STANDBY GENERATOR- ALL aXis CONTROLLER
TROUBLESHOOTING HSB
Engine will not crank/turn over
1
HSB set in "OFF" mode.
2
Battery not connected or loose, corroded posts or wires
3
Battery(s) not charged or low charge.
4
Check for active fault code.
5
Defective starter solenoid *
6
Defective starter *
7
Generator ON/OFF switch is in the OFF position.
Generator will crank/turn over but will not start
1
Check for active fault code.
2
Fuel valve(s) turned off.
3
Fuel pressure insufficient*.
4
Weak battery(s).
5
Low oil level.
6
Spark plug wire is disconnected.
7
Defective fuel solenoid/regulator. *
Engine starts, runs rough
1
Fuel pressure insufficient*.
2
Wrong fuel jets.
3
Faulty spark plug, loose spark plug wire.
4
Plugged air cleaner
5
Generator overloaded*.
6
Shorted circuit *
HSB starts, then suddenly stops
1
Check for active fault code.
2
Fuel supply insufficient*
3
Low oil, pressure shut down
4
Generator over loaded
5
Engine high/over temperature shut down
No AC output
1
Circuit breaker in "OFF" position
2
Main circuit breaker in "OFF" position.
3
Transfer switch breaker in "OFF" position.
4
Standby breakers set in "OFF" position.
5
Line circuit tripping breaker because of short circuit *
6
Line circuit tripping breaker because of overload *
MODELS
®
Place the HSB controllers in the AUTO position.
Connect the batteries according to owner's manual, clean and tighten
the battery connections
Recharge or replace battery(s).
Identify fault code, correct and reset.
Check either single or dual generator ON/OFF switches are in the ON
position (inside on 100515 and 100304, on the back for 100304).
Identify fault code, correct and reset.
Turn on fuel supply.
Manometer check, confirm fuel pressure to fuel regulator*.
Recharge or replace battery(s)
Check for oil leaks. Check the oil level and add oil if necessary.
Connect spark plug wire.
Manometer check, confirm fuel pressure to fuel regulator*.
Check jets for NG or LPG, change to correct Master Mixer fuel jets.
Change spark plug, set gap, connect wire.
Clean or replace air cleaner.
Remove one or more loads*.
Identify fault code, correct and reset.
Manometer check, confirm fuel pressure to fuel regulator*.
Check for oil leaks. Check the oil level and add oil if necessary.
Turn off standby circuits for house, reset fault, place unit back into
AUTO and ATS mode. Turn on standby circuits for house. If problem
returns contact Champion or Champion service dealer*.
Check all intake and exhaust ventilation around the HSB, remove all
debris. Let HSB sit for 30 minutes to cool down.
Turn on breaker.
Turn on breaker.
Turn on breaker.
Turn on breaker.
51
TROUBLESHOOTING HSB

Publicidad

loading

Este manual también es adecuado para:

100515