9.1
POWER BOARD FUSE REPLACEMENT
Proceed as indicated below (reserved for qualified technical per-
sonnel only):
• Disconnect the power to the equipment.
• Remove the top cover of the equipment and then the power
board cover.
• Remove the fuse cap, then the fuse, using a suitable screw-
driver.
• Install a new IEC-60127-2/II certified time-delay 5 A fuse
(T5AL250V), then refit the protective cap.
• Reassemble all the plastics and make sure the equipment is
correctly installed before powering it.
9.2
REPLACEMENT OF ELECTRIC Heater SAFETY
THERMOSTAT
This equipment has a manual-reset safety thermostat connect-
ed in series with the heating element immersed in water, which
interrupts the power supply in case of overtemperature inside
the tank.
If necessary, proceed as follows to reset the thermostat (re-
served for qualified technical personnel):
• Unplug the product.
• Remove any air ducts.
• Remove the top cover by first undoing the locking screws (fig.
73).
• Remove the front panel and manually reset the tripped safety
thermostat (fig. 74). In case of intervention, the central pin of
the thermostat comes out by about 2 mm.
• Refit the previously removed top cover.
200 HT - 260 HT
fig. 72
cod. 3540000420 - Rev. 03 - 09/2023
fig. 73- Top cover removal
fig. 74- Front panel removal
The intervention of the safety
thermostat may occur due to a
fault in the control board or the
ATTENTION
absence of water in the boiler
tank.
NB!: The intervention of the thermostat ex-
cludes the operation of the electrical heater
but not the heat pump system within the al-
lowed operating limits.