TN
Limite Superior = Superior Limit
Tensão Nominal = Nominal Tension
Tensão da Rede = Network Tension
Limite Inferior = Inferior Limit
Falta de Energia = No Power
Limite Interrupção = Interruption Limit
Registro Inválido: Afundamento = Invalid registry: sinking
Registro Inválido: Elevação = Invalid registry: elevation
In the interval 1is a valid registry, since the nominal tension is within the
acceptable limits. In the interval 2 the nominal tension is below the sinking limit by less
than 3 seconds, this way been considered as a tension sinking, therefore it will be
computed one invalid registry. The same situation happens in the moment 3 but with a
tension increase. At interval 4 the registry will be valid, since the nominal tension
remains for more than 3 seconds below the configured limit. At interval 5 is a valid
registry, because the nominal tension is within the acceptable limits.
At interval 6 and 7 the value of nominal tension is below the percentile (%) of
tension Interruption, been considered an invalid registry.
Every time that the nominal tension remains out of the configured limits, for a
time also larger than the configured, the registry will be considered as valid. Every time
that the nominal tension crosses the tension limits configured, for a time smaller than
configured , the registry will be considered invalid and the analysis software will not
consider it.
Obs.: the PT primary is defined as the reference for nominal tension.
If the nominal tension is equal to 127 V, the PT primary must be configured with the
same value.
8. THE ANALYZER SOFTWARE
The ANALYZER SOFTWARE IMS is utilized by the PowerNET P-600, having
the purpose of read, download and analyze the data stored in the equipment through
the serial communication port, as well as make the parameters programming when
necessary.
PowerNET P-600