Congratulations for having chosen a Gewiss product. Gewiss products are constructed with careful attention to detail, using only
high quality materials.
Gewiss products will guarantee optimal performance over time.
Read these instructions carefully.
They contain important information on how to install and operate the system.
The installers should hand them over to the end users and ask them to read them carefully as well.
In case of a breakdown or malfunctioning, please contact an authorized technician or GEWISS' SAT helpdesk.
GEWISS reserves the right, in its sole discretion, (at all times and without prior notice), to make any changes to its products that
it deems necessary for technological or manufacturing purposes, or as an improvement in use or performance.
1. The activo control system is a device that tests the status of the circuit breakers and residual current devices connected to it
and indicates any faults in the installation or excessive current consumption.
The activo control system itself does not protect the installation. Protection is provided only by the circuit breakers and residual
current devices connected to it.
A failure and / or malfunctioning of the elecronic module do not affect the safety of the installation.
2. The activo control system is not an approved measuring device and is therefore not suitable for professional measuring of the
electrical parameters indicated.
3. Disconnect from the power supply upstream of the control system before removing the electronic module and at all times
before servicing the activo control system. This work shall be carried out only by skilled technical staff.
4. For phase to phase network applications, contact the technical service beforehand.
5. Proper control of the alarms can be assured only by suitably programming the activo control system.
If one requires an alarm signal to be sent out before the connected circuit breakers and residual current devices trip, the
settings entered must be lower than the installation parameters.
Example:
TYPE OF ALARM
MAX CAPACITY EXCEEDED
MAX LEAKAGE EXCEEDED
Attention - Important
Instructions for use
INSTALLATION SETTING
3KW
30mA
3
SETTING TO BE ENTERED
2,5KW
15mA