Refrigerant (for R32 Only)
WARNING
• The appliance shall be stored in a well-ventilated
area where the room size corresponds to the room
area as specified for operation.
• The appliance shall be stored in a room without
continuously operating open flames (for example
an operating gas appliance) and ignition sources
(for example an operating electric heater).
• The appliance shall be stored so as to prevent
mechanical damage from occurring.
• Do not use means to accelerate the defrosting
process or to clean, other than those
recommended by the manufacturer.
• Do not pierce or burn.
• Be aware that refrigerants may not contain an
odour.
• Pipe-work shall be protected from physical
damage.
14
Minimum Floor Area
Refer the minimum floor area depending on the
installation height. If outdoor units are installed
indoors, outdoor units also meet the minimum floor
area.
Minimum Floor Area (m
m (kg)
Floor
Standing
< 1.224
-
1.224
12.90
1.4
16.82
1.6
21.97
1.8
27.80
2.0
34.32
2.2
41.53
2.4
49.42
• m: Total refrigerant amount in the system
• Total refrigerant amount: Factory refrigerant
charge + Additional refrigerant amount
NOTE
• The actual refrigerant charge is in accordance
with the room size within which the refrigerant
containing parts are installed.
• The ventilation machinery and outlets are
operating adequately and are not obstructed.
• If an indirect refrigerating circuit is being used,
the secondary circuit shall be checked for the
presence of refrigerant.
• Marking to the equipment continues to be visible
and legible. Markings and signs that are illegible
shall be corrected.
• Refrigeration pipe or components are installed in
a position where they are unlikely to be exposed
to any substance which may corrode refrigerant
containing components, unless the components
are constructed of materials which are inherently
resistant to being corroded or are suitably
protected against being so corroded.
EN
)
2
Wall
Ceiling
Mounted
Mounted
-
-
1.43
0.956
1.87
1.25
2.44
1.63
3.09
2.07
3.81
2.55
4.61
3.09
5.49
3.68