Bleeding
The air and humidity left inside the refrigerant
circulation can cause compressor malfunction. After
having connected the indoor and outdoor units, bleed
the air and humidity from the refrigerant circulation
using a vacuum pump.
Service port
1
Unscrew and remove the caps from the 2-way
and 3-way valves.
2
Unscrew and remove the cap from the service
port.
3
Connect the vacuum pump hose to the service
port.
4
Operate the vacuum pump for 10 - 15 minutes
until an absolute vacuum of 10 mm Hg has been
reached.
5
With the vacuum pump still in operation, close
the low - pressure knob on the vacuum pump
coupling. Stop the vacuum pump.
6
Open the 2-way valve by 1/4 turn and then close
it after 10 seconds. Check all the joints for leaks
using liquid soap or an electronic leak device.
7
Turn the body of the 2-way and 3-way valves.
Disconnect the vacuum pump hose.
8
Replace and tighten all the caps on the valves.
22