INFORMATION FOR THE INSTALLER
Charging the Refrigerant
Fixed-Speed Type Model
Liquid
Gas pipe
Model
pipe
diameter
diameter
1/4"
W09TI
(Ø 6.35)
(Ø 9.52)
1/4"
W09TE
(Ø 6.35)
(Ø 9.52)
1/4"
W12TI
(Ø 6.35)
(Ø 9.52)
1/4"
W12TE
(Ø 6.35)
(Ø 9.52)
1/4"
W18TI
(Ø 6.35)
(Ø 9.52)
1/4"
W24TI
(Ø 6.35)
(Ø 12.70)
(1) Refer to the data rating label sticked on the outdoor unit.
Tightening Torque for Protection Caps and Flange Connection
Tightening torque
Pipe
(N x m)
1/4" (Ø 6.35)
14 - 18
3/8" (Ø 9.52)
34 - 42
1/2" (Ø 12.70)
49 - 61
5/8" (Ø 15.88)
68 - 82
NOTE
• The amount of refrigerant charged is based on the standardized pipe length. If the installed pipe is longer than
the standard length, extra refrigerant needs to be added.
• Reliability cannot be guaranteed if the pipe is longer than the maximum length.
• It may cause reliability, performance, noise, and vibration problems, if piping limitations are not met. Ensure
there's a minimum piping length, by making loops if necessary, if the indoor unit and outdoor unit are too close.
24
Maximum
Lenght
distance
of pipe
between
with
indoor
standard
and
charge
outdoor
unit
3/8"
5 m
15 m
3/8"
5 m
15 m
3/8"
5 m
15 m
3/8"
5 m
15 m
3/8"
5 m
15 m
1/2"
5 m
15 m
Corresponding stress
(using a 20 cm wrench)
Wrist strength
Arm strength
Arm strength
Arm strength
Max. diff.
in level
Additional
between
refrigerant
indoor
charge
and
outdoor
unit
15 g/m
10 m
15 g/m
10 m
15 g/m
10 m
15 g/m
10 m
25 g/m
10 m
16 g/m
10 m
Service port nut
Protection caps
EN
Refrigerant
Type of
charge at
refrigerant
maximum
(1)
pipe length
0.720 kg
R32
0.600 kg
R32
0.690 kg
R32
0.640 kg
R32
1.250 kg
R32
1.160 kg
R32
Tightening torque
(N x m)
20 - 25
10 - 12