Fig. 7: Shunt release connection
XG3
3
1
Fig. 8: Schematic circuit diagram: Connecting an ex-
ternal shunt release
u Strip the cable.
u Strip the conductors 10 mm.
u Connect the conductors to the plug connector
(included in the scope of delivery).
u Insert the plug connector into XG3.
Terminal
Connection
(XG3)
5
Shunt release
6
Power supply
n Max. 230 V AC or max. 24 V DC
n Max. 1 A
u Comply with the connection data for the switch-
ing output.
1 "4 Technical data" [} 11]
1
3
Shunt release
AC/DC
u Route the line as shown in the illustration above
and secure it to the marked components using
cable ties (included in the scope of delivery).
In the event of a fault (welded load contact),
the shunt release is activated and the
product is disconnected from the mains.
5.7
Connecting the data line (Modbus RTU)
The tasks described in this section may only
be carried out by a qualified electrician.
The product can be connected to an external en-
ergy meter or an energy management system via
Modbus RTU.
MENNEKES recommends using the data lines be-
low:
n With a line length of 40 m, a network cable
(CAT-6 / CAT-7) can be used. It can be useful to
use a network cable so that your installation is
ready to accommodate future developments.
Not all wires are required.
n PROFIBUS cable
n For installation in the ground: Siemens
PROFIBUS line, underground cable
6XV1830-3FH10 (manufacturer EAN
4019169400428)
n For installation without mechanical stress:
Siemens PROFIBUS line 6XV1830-0EH10
(manufacturer EAN 4019169400312)
Data lines must not exceed a length of 100 m.
EN
19