Process Data (Pd) - Balluff BML SL1-ALZ Serie Manual De Instrucciones

Ocultar thumbs Ver también para BML SL1-ALZ Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

BML SL1-ALZ _ -U_ ZZ- _ U1L - _ _ _ _
Absolute magnetic encoder system
7
IO-Link Smart Sensor Profile Ed. 2 (BML SL1-ALZ1-UE/MZZ-_U1L-...) (continued)
7.2

Process data (PD)

The variants of the BML use the IO-Link interface to output
a cyclical measurement value along with status and
switching point information.
Byte
5
4
3
Measured value
Tab. 7-2:
Process data
Measurement value
The measurement value represents the position of the
sensor head in μm and consists of a signed 32-bit value.
Scaling factor
The scaling factor is a constant, signed 8-bit number
which indicates the power of ten by which the
measurement value must be multiplied in order to convert
it into the SI unit of meters.
For the BML the scaling factor is –6 (0xFA):
Measurement value × 10
= Position [m]
−6
Status and SSC
Bit Name
Function
7
System Error
The BML is no longer functional
(memory error, hardware defect).
6
Out of Range /
The BML is not detecting a
No
magnetic tape within the
Measurement
detection range.
Data
5
not used
4
Measurement
The sensor head is within the set
Value Unsafe
measuring range but the excess
gain is too low. The threshold for
the signal can be set using the
parameter Low Signal Quality
Threshold (see Section 7.5.11).
(Available only for
BML SL1-ALZ1-UEZZ-_U1L-...)
3
SSC 4
Switching information for the
fourth switching point
2
SSC 3
Switching information for the third
switching point
1
SSC 2
Switching information for the
second switching point. In SIO
mode SSC2 is placed on OUT2.
0
SSC 1
Switching information for the first
switching point. In SIO mode SSC
1 is placed on OUT 1.
Tab. 7-3:
Status and SSCs
www.balluff.com
2
1
0
Status
Scaling
and
factor
SSCs
While the sensor head cannot provide current process
data, the process data are designated as invalid using the
PD Invalid Bit. It can happen that during configuration no
measurement can be performed, so that no current
measurement data are able to be output. Output of the PD
Invalid Bit can be disabled (see Diagnostics suppression
on page 35).
The IO-Link functionality PD Invalid Bit is
handled differently by different IO-Link masters
(see manual for the master used). Output of the
PD Invalid Bit can be suppressed using the
parameter Diagnosis Suppression (see
Diagnostics suppression on page 35).
Measuring range
Status bits
1)
Bit 4 0 0
Bit 6 1 1
see Tab. 7-3
1)
If this bit is set, the excess gain is too low. The magnetic tape is
2)
damaged or offset too far.
Fig. 7-1:
Ranges and output
If the BML is still on the magnetic tape but outside the
detection/measuring range, the process data variable is
replaced by the following values:
Out of Range positive: 2'147'483'640 (0x7FFFFFF8)
Out of Range negative: –2'147'483'640 (0x80000008)
A measurement error occurs if no magnetic tape is
detected, the functional space is not maintained (see
Tab. 4-2 on page 11) or the sensor head is not
completely on the measuring tape. In this case the process
data variable is replaced by the error value 2'147'483'644
(0x7FFFFFFC) (No Measurement Data).
Position
0/1
0 0
2)
0
1 1
english
25