LU-VE Emeritus LU1W Manual De Usuario página 142

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PH13
Maximum full-scale value
for spray supply water
0x080C
2061
pressure probe
PH14
Minimum full-scale value
for wet resources water pH
0x080D
2062
transducer
PH15
Maximum full-scale value
for wet resources water pH
0x080E
2063
transducer
PH16
Minimum full-scale value
for wet resources water
0x080F
2064
conductivity transducer
PH17
Maximum full-scale value
for wet resources water
0x0810
2065
conductivity transducer
PH19
0x0812
2067
Main Control Probe
PH21
Water spray pressure
0x0814
2069
probe type
PH23
Adiabatic Panels flow
0x0816
2071
meter model
PH24
Wet resources supply
water pH measurement
0x0817
2072
probe type
PH25
Wet resources supply
water conductivity
0x0818
2073
measurement probe type
2.3.2
Enable Water Inlet Temperature Probe
In the case of a dry cooler, it is possible to enable, via parameter PH19, an optional temperature probe that measures
the inlet water temperature to the exchanger. The temperature detected has no effect on the regulation, but results
usable to user through the Probes screen or by MODBUS.
The ambient temperature and indoor temperature probes too can be disabled by parameters PH18 and PH09
respectively.
Attention: disabling these probes heavily impacts on the management of spray and adiabatic panels, and on the
antifreeze functions implemented by the controller. Proceed to these settings with extreme caution; the user
becomes responsible for any malfunctions or breakages, caused by the low temperature, which may occur.
LU1W - User Manual
Data Type and Notes
[unit of measure as set by
PH03, default bar]
- short int
- short int
- short int
[μS/cm]
- unsigned short int
[μS/cm]
- unsigned short int
0 = NTC
1 = 4..20mA
- unsigned short int
0 = 0-10V
1 = 4..20mA
- unsigned short int
0 = DN6; 1 = DN8;
2 = DN10; 3 = DN11;
4 = DN15; 5 = DN20;
6 = DN25; 7 = DN32
- unsigned short int
0 = 0-10V
1 = 4..20mA
- unsigned short int
0 = 0-10V
1 = 4..20mA
- unsigned short int
19
Default
Min
Max
value
7.0
PH12
290.0
-2.0
-2.0
PH15
16.0
PH14
16.0
0
0
PH17
5000
PH16
10000
0
0
1
1
0
1
0
0
7
1
0
1
1
0
1
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
0.0
Holding
0.0
Input
0.0
Input
0
Input
0
Input
0
Input
0
Input
0
Input
0
Input
0
Input

Publicidad

Tabla de contenido
loading

Tabla de contenido