MODBUS
MODBUS
Nome e Descrizione
Base 0
Base 1
Parametro
Pd46_enManAO3_lampUVPA
0x0BCF
3024
Abilita forzatura AO3
Pd47_enManAO2_PA
0x0BD0
3025
Abilita forzatura AO2
Pk45_forceManAO1_Fan
0x0BD2
3027
Valore simulato AO1
Pk46_forceManAO3_lampUVPA
0x0BD3
3028
Valore simulato AO3
Pk47_forceManAO2
0x0BD4
3029
Valore simulato AO2
Pd60_enManDO_Alarm
0x0BD6
3031
Abilita forzatura DO11
Pd61_enManDO_Spray1
0x0BD7
3032
Abilita forzatura DO3
Pd62_enManDO_Spray2
0x0BD8
3033
Abilita forzatura DO4
Pd63_enManDO_Spray3
0x0BD9
3034
Abilita forzatura DO5
Pd64_enManDO_Spray4
0x0BDA
3035
Abilita forzatura DO6
Pd65_enManDO_Pump
0x0BDB
3036
Abilita forzatura DO2
Pd66_enManDO_Pasx
0x0BDC
3037
Abilita forzatura DO8
Pd67_enManDO_Padx
0x0BDD
3038
Abilita forzatura DO9
Pd68_enManDO_WaterRamp
0x0BDE
3039
Abilita forzatura DO7
Pk60_forceManDO_Alarm
0x0BE0
3041
Valore simulato DO11
Pk61_forceManDO_Spray1
0x0BE1
3042
Valore simulato DO3
Pk62_forceManDO_Spray2
0x0BE2
3043
Valore simulato DO4
Pk63_forceManDO_Spray3
0x0BE3
3044
Valore simulato DO5
Pk64_forceManDO_Spray4
0x0BE4
3045
Valore simulato DO6
LU1W – Manuale utente
Valore di
Tipo Dato e Note
default
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
[%]
- unsigned short int
0.00
[%]
- unsigned short int
0.00
[%]
- unsigned short int
0.00
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0 = disabilitata,
1 = abilitata
- unsigned short int
0
0=OFF, 1=ON
- unsigned short int
0
0=OFF, 1=ON
- unsigned short int
0
0=OFF, 1=ON
- unsigned short int
0
0=OFF, 1=ON
- unsigned short int
0
0=OFF, 1=ON
- unsigned short int
0
82
Posizioni
Min
Max
decimali
0
1
0
0
1
0
0.00
100.00
0.00
0.00
100.00
0.00
0.00
100.00
0.00
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
REV.1.1 – 16/10/2017 - ITA
Tipo
Registro
MODBUS
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding
holding

Publicidad