Cleaning The Exchanger - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

8.3
The cleaning function of the exchanger activates the fans with an inverted rotation direction. The function only starts
when the unit is on.
Cleaning can be programmed via parameter PC01; cleaning is performed daily or weekly, depending on the setting:
Daily cleaning: with parameter PC01 = 1, cleaning is performed every day at the preset time (parameter
PC02).
Weekly cleaning: with parameter PC01 = 2, cleaning is performed weekly on the set day (parameter PC03)
and set time (parameter PC02).
When the cleaning procedure is activated, the fans are switched off for a fixed time of 60 seconds and then turned on
for anti-rotation PC05. After finishing the procedure, they remain off for a further 60 seconds before returning to the
normal setting.
You can also start the cleaning cycle manually from the ADVANCED → MANUAL menu. On the CLEANING screen, move
the cursor over the UP and DOWN keys in the Fans window to Run, then press ENTER.
PARAMETER
NAME
Cleaning activation and frequency:
0 = No (Disabled)
PC01
1 = Daily
2 = Weekly
PC02
Cleaning start time
Cleaning day:
0 = Sunday
PC03
1 = Monday
---
6 = Saturday
PC04
Fan speed in cleaning mode
PC05
Cleaning cycle time
MODBUS Registers
MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PC01
Cleaning activation and
0x07E4
2021
frequency
LU1W - User Manual

Cleaning the exchanger

DESCRIPTION
Data Type and Notes
0 = No (Disabled)
1 = Daily
2 = Weekly
- unsigned short int
DEFAULT
MIN
VALUE
VALUE
No
No
23:00:00
0:00:00
Sunday
Sunday
100.00
0.00
60
1
Default
value
0
75
MAX
UM
VALUE
-
USER → CLEANING
Weekly
hh: mm: ss
USER → CLEANING
23:59:59
-
USER → CLEANING
Saturday
%
USER → CLEANING
PF20
sec
USER → CLEANING
9999
Decimal
Min
Max
positions
0
2
REV.1.1 – 07/11/2017 - ENG
MENU
MODBUS
Register
Type
0
holding

Publicidad

Tabla de contenido
loading

Tabla de contenido