Instead, for each PE08 duration where the ambient temperature remains above PE03 + differential PE04, the
condensing set-point increases an offset equal to PE02 parameter, until the maximum PR02 value is reached.
Ambient
Temp. AI4
PE03
SP
PE02
(set point max)
PE09
(set point min)
Enabling the set-point control via digital input DI2 prevails over the variable set-point setting based on outdoor
temperature.
The set-point in use can be displayed on the VENTILATION screen and via MODBUS via the actSetC parameter.
PARAMETER
NAME
Cooling/condensing set-point
PR02
(summer)
Minimum cooling/condensing set-
PE09
point (winter)
Upper limit of cooling/condensing
PR21
set-point
Lower limit of cooling/condensing
PR22
set-point
PH32
Enable DI2 setpoint selection
LU1W - User Manual
PE04
PE08
PE02
DESCRIPTION
Floating Set-point
DEFAULT
MIN
VALUE
VALUE
45.0
PR22
35.0
PR22
65.0
PR22
10.0
-10.0
No
No
32
MAX
UM
VALUE
°C
PR21
PR02
°C
°C
95.0
°C
PR21
Yes
-
REV.1.1 – 07/11/2017 - ENG
time
time
MENU
USER
USER
ADVANCED →
REGULATION
ADVANCED →
REGULATION
ADVANCED →
VARIOUS