ITT PS200 v5 Guía De Configuración página 175

Publicidad

A
NO DIRECT SUNLIGHT
3300 ft (1000 M)
B
NEMA1/NEMA12
104
o
F (40°C)
MAX
5
F (-15° C)
o
MIN
ACS800-PC NEMA 1
5-95% RELATIVE
HUMIDITY
NO CONDENSATION
NO CORROSIVE GASES
ACS800-PC NEMA 1 and NEMA 12 Dimensions
NEMA 1
A
Frame
Refer to Hardware
B
Inches
Manual Technical
Size
Inches
[mm]
Data for
[mm]
application
guidelines outside
31.7
85.9
of the above listed
R7
[806]
[2181]
limits
31.7
85.9
R8
NEMA1 / NEMA12
[806]
[2181]
12 in. for fan replacement
15 in.
UL Type 1
UL Type 12
Top clearance
Space Requirement For Door
Opening
31.5 in
(800mm)
PS200 UL INSTALLATION QUICK REFERENCE - Floor Mount Units (ACS800-PC)
C
A
C
B1
ACS800-PC NEMA 12
Weight
NEMA 12
C
NEMA 1
NEMA 12
B1
Inches
Lbm
Lbm
Inches
[kg]
[kg]
[mm]
[mm]
93.6
25.9
695
740
[2377]
[659]
[315]
[336]
93.6
25.9
945
990
[2377]
[659]
[429]
[449]
Fastening points when
Installed back against back
To another cabinet
Fastening points when installed back against wall
L-bracket
M12 bolt
Cabinet top
Fastening cabinet at top using L-bracket (side view)
Alternate (when fastening at back is not possible)
NEMA1 / NEMA12
Review the entire hardware manual prior to installation.
Failure to follow these instructions may result in serious
personal injury,death and/or equipment damage
The information provided on this sheet is for installation
reference only. Please refer to
ACS800-PC Installation Manual for additional installation
details
Mains / Power Wiring Schematic
Circuit
Class T Fuses
Breaker
Supplied by ITT
U1 V1 W1
U2 V2 W2
PE
T2
L1 L2 L3
T1
T3
Motor
3
Power
Supply
Metallic Conduit
or Shielded
Cable
General Notes:
1.-360 Grounded terminations are required
2. Standard T type fuses or Ultra-rapid fuses are required to
Protect drive. Fuse operating times should be less than 0.5
Sec. Refer to Technical Data Section for details
12 in. (300mm)
Motor
minimum
Cable
Input
Ground
Power
ACS800
Lug Bar
3 Phase Supply 380V, 400V
Cable
415V, 440V, 460V, 480V or 500V
Motor
Frame
Terminals
R7
Input Power
Terminals
R7
R8
Terminal Strip
R8
R8
R8
R8
ACS 800-PC
R8
NEMA 1
R8
Typical
R8
* Control cables shall be 8 in. (200mm) minimum
From input power cable and 20 in. (500mm)
minimum from motor cable.
Control cables shall cross perpendicular to power
And motor cables
Input and Motor Cable terminal sizes (per phase) and tightening torques are given
below. Two hole cable lugs (½ inch diameter) can be used.
U1,V1,W1,U2,V2,W2
FRAME
Tightening
Max Cable
SIZE
Screw Size
Kcmil/AWG
2 x 250
R7
½ inch
MCM
3 x 350
R8
½ inch
MCM
Installation Checklist
MECHANICAL
1. Check that the ambient operating conditions are suitable [Technical Data].
2 Check that drive enclosure is suitable for installation location. Install in a non-hazardous location only.
3. Check that the unit is mounted properly on a vertical non-flammable wall [Mechanical Installation].
4. Check that cooling air flows freely.
5. Check the applicability of the motor and the driven equipment [Electrical Installation].
ELECTRICAL
5. If the PS200 is connected to an IT (ungrounded) power system, check that the EMC filter capacitors are disconnected.
6. The Capacitors are reformed if stored over 1 year.
7. Check that the drive is grounded properly.
8. Check that the input voltage matches the drive nominal input voltage.
9. Check that the input power connections at L1, L2, and L3 and tightening torques are OK.
10. Check that the appropriate line fuses and disconnect means are installed.
11. Check that motor connections at U2, V2, and W2 and tightening torques are okay.
12. Check the motor cable routing.
13. Check that there are no power factor compensation capacitors connected between the drive and the motor.
14. Review and check that control connections inside the drive are properly wired [See control wiring diagrams].
15. Set the fan voltage transformer and NEMA 12 Fan Transformer (if present).
16. Check that there are no tools or foreign objects or dust from drilling left inside the drive.
17. With bypass connection, check that input line voltage cannot be applied to the output of the PumpSmart PS200.
18. Drive, motor connection box and other covers are in place.
Drawing is not to scale
Drawn: JCS 6-2-06
Rev1 Format Update
Dimensions in inches
[mm]
Checked: 6-2-06
Fuse (600v)
Input
UL Class T
Bussmann
Size
Current (A)
(A)
Type
-0170-5
175
300
JJS - 300
-0210-5
220
300
JJS - 300
-0270-5
400
JJS - 400
293
-0300-5
331
400
JJS - 400
-0320-5
397
600
JJS - 600
467
-0400-5
600
JJS - 600
-0440-5
501
800
JJS - 800
-0490-5
542
800
JJS - 800
-0550-5
614
800
JJS - 800
-0610-5
661
800
JJS - 800
EARTHING PE
Tightening
torque
Screw Size
torque
lbf ft
lbf ft
37...55
3/8 inch
22...32
37...55
3/8 inch
22...32
Issue
REV
B05414A
SHEET 1 OF 1
1
-