Planos Del Control - metso ND9000H Instrucciones De Instalacion, Mantenimiento Y Funcionamiento

Controlador de válvula inteligente
Tabla de contenido

Publicidad

7 ND90 70 es
12.12

Planos del control

ND9100H, ND9300H
NONHAZARDOUS LOCATION
Exi barrier
Uout max 28 V
Iout max 120 mA
Pmax 1 W
Exi barrier
Uout max 28 V
Iout max 120 mA
Pmax 1 W
FM Notes:
1.
The Intrinsic Safety Entity concept allows the interconnection of two Intrinsically safe devices Approved by
FM Approvals with entity parameters not specifically examined in combination as a system when:
Uo or Voc or Vt ≤ Vmax, Io or Isc or It ≤ Imax, Ca or Co ≥ Ci + Ccable, La or Lo ≥ Li + Lcable, Po ≤ Pi.
2.
Dust-tight conduit seal must be used when installed in Class II and Class III environments.
3.
Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc.
4.
Installation should be in accordance with ANSI/ISA RP12.06.01"Installation of Intrinsically Safe Systems
for Hazardous (Classified) Locations" and the National Electrical Code® (ANSI/NFPA 70) Sections 504 and 505.
5.
The configuration of associated Apparatus must be FM Approved under Entity Concept.
6.
Associated Apparatus manufacturers installation drawing must be followed when installing this equipment.
7.
No revision to drawing without prior Approval by FM Approvals.
8.
The enclosure must be bonded.
9.
Nonincendive wiring concept: The Nonincendive wiring concept allows the interconnection of devices with
Nonincendive wiring parameters: Vmax = 30V, Ci =22 nF, Li =53 µH
10.
Nonincendive wiring parameters: Voc or Vt ≤ Vmax, Ca or Co ≥ Ci + Ccable, La or Lo ≥ Li + Lcable.
11.
The configuration of Associated Nonincendive Field Wiring Apparatus must be FM Approved under
Nonincendive wiring concept.
12.
Associated Nonincendive Field Wiring Apparatus manufacturers installation drawing must be followed when
installing this equipment.
HAZARDOUS LOCATION
Shrink tubes are
recommended to
avoid short-circuits
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 0, AEX ia, Group IIB/IIC T4/ T5/T6
T4: Ta = -40...80 °C
T5: Ta = -40...65 °C
T6: Ta = -40...50 °C
Position Transmitter
Li
53 µH
Ci
22 nF
Imax 120 mA
Umax 28 V
Pmax 1 W
Shield terminal is without any
electrical connection. If wanted,
shields can be connected to this terminal
Li
53 µH
SHD
Ci
22 nF
Imax 120 mA
Umax 28 V
Pmax 1 W
ND9100H_T
ND9300H_T
53