BIP LD2-T017-01-EP _ _ / EP _ _ -S4
Inductive Positioning System
4
Installation and connection
4.1
Installation instructions
In order to prevent effects on the measurement signal by
the installation material, a metal-free area around the active
surface of the BIP of approximately 5 mm must be
maintained (see Fig. 4-1 and Fig. 4-2).
If the BIP detects not only the magnet, but also another
metal piece, invalid measurement signals will result.
To obtain a measurement signal with high resolution,
suitable cable routing in the machine and filter measures
for system power supply must be ensured.
The magnet can be moved in the range
D = 0.5...1.3 mm in front of the active surface in the
direction of measurement (see Fig. 4-3). The resulting
linearity error of the output signal is minimal in the distance
range D = 1.0 ±0.25 mm.
The measuring direction follows the wedge-shaped symbol
(marking on the active surface).
Installation
► Fasten the BIP with 2 mounting screws
DIN EN ISO 4762 M4 x 10 (max. tightening torque:
0.5 Nm).
www.balluff.com
Active surface
Fig. 4-1:
Spacing of metal-free area
25.5
Fig. 4-2:
Installation dimensions
BAM TG-XE-020 magnet
(2)
17.5
Fig. 4-3:
Distance from measuring surface
≥5
8
20
english
7