○ In particular, each alarm memorises:
•
date and time of intervention;
•
alarm code and description;
•
in/out water temperature values as soon as the alarm was triggered;
•
alarm delay time from the switch-on of the connected device;
•
compressor status at the time of the alarm;
○ Advanced functions:
•
set-up for serial connection (KRS485, KFTT10, KBE, KBM, KUSB
accessory);
•
possibility to have a digital input for remote management of
double set point (DSP);
•
possibility of having a digital input to manage total recovery
(RC100), the desuperheater (DS) or for production of domestic hot
water by means of the 3-way diverter valve (VDEV). In this case, there
is the possibility of using a temperature probe instead of the discrete
input (see specific section for more information);
•
possibility to have an analogue input for the shifting Set-point
(CS) via a 4-20mA remote signal;
•
configured to manage time slots and work parameters with the
possibility of daily/weekly operation planning;
•
check-up and monitoring of scheduled maintenance status;
•
computer-assisted unit testing;
•
self-diagnosis with continuous monitoring of the unit functioning
status.
○ Set-point regulation via the AdaptiveFunction Plus with two options:
•
fixed set-point (Precision option);
•
set-point sliding (Economy option).
•
Compressor drive control serial connection to the programmable
electronic board.
II.3
ACCESSORIES
IMPORTANT!
Only Use original spare parts and accessories.
HITECSA shall not be held liable for damage
caused by tampering with or work carried out by
unauthorised personnel or malfunctions caused by
the use of non-original spare parts or accessories.
II.3.1
FACTORY FITTED ACCESSORIES
FDL – Forced Download Compressors Function. Compressor
modulation to limit the absorbed current and power (digital input) Also
used as a "night mode" function to limit noise during night-time
operation
SIL – Silenced set-up (sound-proof compressor compartment +
compressor ear muff)
FI15 – Modulating condensation control with fans with EC motor
(Brushless)
RAP - Unit with copper/pre-painted aluminium condensation coils
BRR – Unit with copper/copper condensation coils
DSP – Double set-point via digital consensus (incompatible with the CS
accessory).
CS – Scrolling set point via analogue signal 4-20 mA incompatible with:
-
DSP accessory (138÷262)
-
RC100 (262)
II.3.1.1
Factory Fitted Accessories 120÷130
RAE – Circulator or pump antifreeze(P0/PI0) resistance (P1)
RAS – Antifreeze heater on the tank
II.3.1.2
Factory Fitted Accessories 138÷262
RAE1 – 27W electric pump antifreeze heater (available for P1-P2- PI1-
PI2- ASP1-ASP2-ASPI1-ASPI2 set ups); used to prevent the risk of the
water inside the pump from freezing when the machine is switched off
(provided the unit is not disconnected from the power supply)
RAE2 – 27W antifreeze electric heater for double motor-driven pumps
(available for DP1-DP2- DPI1-DPI2- ASDP1-ASDP2 set ups); used to
prevent the risk of the water inside the pump from freezing when the
machine is switched off (provided the unit is not disconnected from the
power supply)
IOM_EWMIM-EWMIMH_120a262_207984_200601_ES-EN-FR-DE-IT
RAS - 300W storage tank antifreeze resistor (available for ASP1- ASP2
-ASDP1 -ASDP2 -ASPI1- ASPI2 set ups); to prevent the risk of ice
formation inside the inertial storage tank when the machine is switched
off (as long as the unit is not disconnected from the power supply)
RAB – Base antifreeze heater (heating models)
BRH – Units with copper/aluminium condensing coils with hydrophilic
treatment (for heating models)
V3V – Unit complete with 3-way diverter valve for the production of
domestic hot water. Only available with Pump–single electric pump set
up; not available with DS or RC100
DS - Desuperheater. Also active with winter operation for heating pumps
RC100 - Heat recovery unit with 100% recovery.
LKD – Refrigerant leakage detector
EEM – Energy Meter. Measure and display values of the electrical
units. See specific section for more information
GM - Refrigerant circuit high and low pressure gauges
II.3.2
ACCESSORIES SUPPLIED SEPARATELY
KSA – Rubber anti-vibration mountings
KFA – Water filter
KRIT – Additional electrical resistance for heat pump, controlled by
regulation.
KVDEV – (EWMIMH heat pump 120÷130) 3-way diverter valve for
managing the production of domestic hot water.
(EWMIMH heat pump 138÷262) 3-way valve in protective casing for the
production of domestic hot water, managed by the setting. Only
available with Pump set up, not available with the V3V set up installed
on the machine KEAP – Outdoor air temperature probe for set-point
compensation (as an alternative to the outdoor temperature probe
fitted), incompatible with the CS accessory
KTRD - Thermostat with display (138÷262)
KTR - Remote keypad for control at a distance with LCD display and
same functions as the machine. Connection must be made with a 6-
wire telephone cable (maximum distance 50 m) or with
KRJ1220/KRJ1230 accessories. For greater distances up to 200 m, use
an AWG 20/22 shielded cable (4 wires+shield, not supplied) and the
KR200 accessory
KRJ1220 - Connection cables for KTR (20 m length)
KRJ1230 - Connection cables for KTR (30 m length)
KR200 - Remote Control Kit for the KTR accessory for distances
greater than 50 m and up to 200 m (AWG shielded cable not supplied)
KRS485 - RS485 interface for serial dialogue with other devices
(proprietary control; protocol Modbus RTU)
KFTT10 - LON interface for serial communication with other devices
(LON protocol)
KBE - Ethernet interface for serial communication with other devices
(BACnet IP protocol)
KBM - RS485 interface for serial communication with other devices
(BACnet MS/TP protocol)
KUSB - RS485/USB serial converter (USB cable supplied)
Description and fitting instructions are supplied with each
accessory.
II.4
TRANSPORT - HANDLING AND STORAGE
DANGER!
The unit must be transported and handled by
skilled personnel trained to carry out this type of
work.
IMPORTANT!
Be careful to prevent damage by accidental
collision.
54