For units assembled with Pump set up, the KVDEV kit can be installed for managing the domestic hot water production. The 3-way valve allows
deviating the water flow from the system to the technical water tank for the production of domestic hot water.
The kit includes two flexible pipes to connect the delivery and return of the unit.
The accessory must be mounted the closest possible to the heat pumps, in order to prevent a transfer of cold water inside the domestic hot
water storage, during the passage between heat pump chiller operation to produce domestic hot water.
The delivery and return fittings towards the system are available with 2" connections. The kit is equipped with RAL9018 painted bonnet.
Cable gland for wiring the power supply. IP 54 rate
II.7.12.2 Valve body technical characteristics and servomotor technical data
The diverter valve with nickel-plated bass body, chrome-plated brass ball, PTFE ball seat seal and HNBR manoeuvre rod seal, synthetic fibre (Fasit)
bar hold gaskets.
Maximum differential pressure is: 6 bar Working pressure: PN 40 Flow temperature limits: -40÷100°C
Ball manoeuvre time with 180° angle: 120 s.
The passage of fluid is always guaranteed during the manoeuvre. The actuator is contained in a sealed box fixed to the valve body via a split pin.
Power supply voltage 230 V/50Hz Absorbed power 4 VA.
Isolation class II
Maximum torque: 28 Nm (230V) Auxiliary contact: 6 A 230V (on-off)
1000
10
0,1
100
II.7.12.3 Electrical connection
F
TA N
Connection of KVDEV valve to unit terminal board
IOM_EWMIM-EWMIMH_120a262_207984_200601_ES-EN-FR-DE-IT
Portata (l/h)
1
1
Electrical panel terminal board
2
KVDEV valve
2
100000