Thermomagnetic circuit breaker
A thermomagnetic circuit breaker and/or fuse must be installed on the connection between the inverter and the
electricity grid.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN 1Play TL M
2.5TL M
2.7TL M
3TL M
3.3TL M
3.68TL M
4.6TL M
5TL M
5.5TL M
6TL M
When selecting the protection in an installation you must take into account that its breaking capacity is greater
than the short-circuit current of the grid connection point.
You must take into account when correctly selecting the protection that the ambient working temperature
influences the maximum current permitted by these protections as indicated by the manufacturer.
Residual current device
These inverters are equipped with a residual current monitoring device that disconnects the unit if it detects a
residual fault current according to the electrical safety standards IEC 62109. For this reason, it is not necessary to
include a residual current device between the unit and the electricity grid.
This protection does not detect residual currents produced upstream of the inverter. If, for other reasons, it is
necessary to install a residual current device upstream of the inverter, this must be assigned to trip at a residual
current of at least 30 mA (type A or type B).

5.5. Wiring length

The inverter measures the voltage in its connection terminals. For this reason, the installer must use an AC cable
with a sufficiently low impedance so that increasing the voltage in the cable (between the distribution transformers
and the unit) does not cause the unit to be disconnected due to high voltage.

5.6. Photovoltaic panels

The photovoltaic panels of the installation must be Class A (IEC 61730).
74
Maximum inverter
current
16 A
16 A
16 A
16 A
16 A
26.2 A
26.2 A
26.2 A
26.2 A
ABE2011IQM01_C - Installation and Operation Manual
Preparation for installing the unit
Rated current for the
thermomagnetic circuit
breaker
20 A
20 A
20 A
20 A
20 A
32 A
32 A
32 A
32 A