WaRNiNG
If applicable, put the Panel in the Service Mode
before you do the activities as stated below; refer to
Fig. 6.1H.
Component
action
Panel
Clean with a non-aggressive
detergent
Make sure that the cable
glands are correctly tightened
Make sure that all detachable
screw terminal blocks on the
PC board are connected
Check for firmware updates;
ref. par. 7.2
Activate one cleaning cycle
and make sure that all filter
cartridges are cleaned
For maintenance activities of the connected filter system, fan
and other components, refer to the corresponding manuals.
7.2
Firmware
The latest firmware version is available on the Plymovent
extranet.
FILTERS CLOGGED
Contact your Plymovent distributor to get the latest
firmware version.
Download the firmware to an empty USB stick.
Follow the flowchart FIRMWARE UPDATE on page 82.
FILTERS VERSTOPT
FILTER GESÄTTIGT
Explanatory notes:
NO COMPRESSED AIR
FILTRES OBSTRUÉS
A
Put the USB stick in the USB port on the PC
board (refer to Fig. 2.1C).
FILTROS OBSTRUIDOS
B
The white LED shows a "heartbeat" blinking
pattern (the system is starting up).
FAN/MOTOR FAILURE
C
When the white LED is blinking, the system has
GEEN PERSLUCHT
recognized the USB stick and the firmware
update is running.
KEINE DRUCKLUFT
D When the white LED is still blinking and the
ABSENCE D'AIR COMPRIMÉ
green LED is on, the firmware update has been
FALTA DE AIRE COMPRIMIDO
successful.
VENTILATOR-/MOTORSTORING
E
When the white LED is still blinking and the red
VENTILATOR-/MOTOR-AUSFALL
LED is on, the firmware update has failed.
EXTERNAL DEVICE
DÉFAUT MOTEUR/VENTILATEUR
Possible causes:
FALLO DEL VENTILADOR/MOTOR
- failure during the update process
- corrupt update files on the USB stick
- you have tried to upload an older firmware
version than the existing one
EXTERN APPARAAT
- you have tried to upload firmware for another
type of Panel, e.g. ControlPro/HMI
EXTERNES GERÄT
F
When the white LED is on before you have
DISPOSITIF EXTERNE
finished the firmware update procedure, the
DISPOSITIVO EXTERNO
firmware update has failed.
Possible causes:
- the Panel does not recognize the USB stick
- the USB stick contains files that are not meant
for the ControlGo Panel
The system goes back to normal mode.
COMMUNICATION ERROR
tip
- Write the date and firmware version in the table
on page 82 to know the latest update; or
- Put a sticker inside the Panel door and write down
the same information.
COMMUNICATIEFOUT
KOMMUNIKATIONSFEHLER
ERREUR DE COMMUNICATION
0000112607/170717/0 ControlGo
ERROR DE COMUNICACIÓN
8
If the system does not function (correctly), consult the
checklist below to see if you can remedy the error yourself.
Should this not be possible, contact your supplier.
Frequency:
every X months
X=3
X=12
X
8.1
X
Symptom
X
WARNING: yellow LED blinking
X
X
FILTERS CLOGGED
You must still solve the cause of the warning. If you do not, the
warning LED remains blinking.
FILTERS VERSTOPT
NO COMPRESSED AIR
FILTER GESÄTTIGT
FILTRES OBSTRUÉS
FILTROS OBSTRUIDOS
+ buzzer during
GEEN PERSLUCHT
FAN/MOTOR FAILURE
KEINE DRUCKLUFT
COMMUNICATION ERROR
ABSENCE D'AIR COMPRIMÉ
FALTA DE AIRE COMPRIMIDO
VENTILATOR-/MOTORSTORING
EXTERNAL DEVICE
VENTILATOR-/MOTOR-AUSFALL
COMMUNICATIEFOUT
DÉFAUT MOTEUR/VENTILATEUR
KOMMUNIKATIONSFEHLER
FALLO DEL VENTILADOR/MOTOR
ERREUR DE COMMUNICATION
ERROR DE COMUNICACIÓN
EXTERN APPARAAT
EXTERNES GERÄT
DISPOSITIF EXTERNE
DISPOSITIVO EXTERNO
SERVICE MODE
SERVICEMODUS
SERVICE-MODUS
MODE DE SERVICE
MODO SERVICIO

tRoUBLEShootiNG

WaRNiNG
If applicable, put the Panel in the Service Mode
before you do the activities as stated below; refer to
Fig. 6.1H.
alerts
problem
FILTER CLEANING
5 s
Poor
extraction
capacity
No filter
cleaning
possible
actual filter
cleaning
One or more
filter modules
are not
cleaned
5
.
SEC
No pressure
controlled
filter cleaning
All automatic
functions are
disabled
possible
Solution
cause
Two functions:
- to suppress the buzzer (if
applicable)
- to reset the warning LED
NO COMPRESSED AIR
Filter cartridges
- Replace the filter
are clogged
cartridges (refer
to the MDB/SCS/
EDS manual)
GEEN PERSLUCHT
- Reset the precoat
COMMUNICATION ERRO
KEINE DRUCKLUFT
timer (ref. par.
6.1 F)
ABSENCE D'AIR COMPRIMÉ
No compressed
Repair the
FALTA DE AIRE COMPRIMIDO
air available
compressed air
connection/supply
Compressed air
pressure too
COMMUNICATIEFOUT
EXTERNAL DEVICE
low
!
KOMMUNIKATIONSFEHLER
Compressed air
Connect or replace
SERVICE MODE
ERREUR DE COMMUNICATION
switch loose or
the compressed air
defective
ERROR DE COMUNICACIÓN
switch
Communication
- Make sure that all
error to one or
SlaveBoard
EXTERN APPARAAT
more filter
connections are
EXTERNES GERÄT
modules
correct; ref. par.
SERVICEMODUS
DISPOSITIF EXTERNE
4.4.3 and 4.4.4
SERVICE-MODUS
- Make sure that all
DISPOSITIVO EXTERNO
DIP switches are
MODE DE SERVICE
correctly
MODO SERVICIO
addressed (ref.
Fig. 4.12 and Fig.
4.13)
Defective
Repair or replace
SlaveBoard
the cable(s)
cable(s) (cable
#1 or #2)
PC board inside
Replace the PC
SlaveBoard(s)
board(s)
defective
Wire bridge on
Put a wire bridge
input IN 4 is
on input IN 4
loose or
missing (in case
the internal
pressure sensor
is used)
External
Connect or replace
pressure sensor
the external
(PT-2500) is
pressure sensor
not connected
or defective
Service Mode
Open the Panel and
put the tumbler
switch to 1
("Normal Mode")
EN - 14