Input Alarm Ht1 - Fusable; Overtemperature Alarm; Black-Out Alarm; Compressor Preventative Maintenance Alarm - Sammic ABS-15/2 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

time the scrolling text "AL08 - KRIWAN COMPRESSORE
-COMPRESSOR KRIWAN" will appear.
Flashing RED symbol (14)
Reset: Pressing the off beeper alarm silencer button or
switching off and switching on the card again (stand-by).

16.8 Input alarm HT1 - fusable

Cause: When the alarm is activated for more than 5 sec-
onds.
Effect: electrical disconnection of certain components
downstream of the fuse.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "AL09 -
CAMBIA FUSIBILE - REPLACE FUSE".
Flashing RED symbol (14)
Reset: It resets itself when the status of the input is acti-
vated.

16.9 Overtemperature alarm

Cause: The overtemperature alarm is activated (only during
storage) when the cell probe detects a certain temperature
value time time greater than the sum of the positive or nega-
tive storage set with the relevant alarm delta (parameter
A2 or parameter A4). The overtemperature alarm is in any
case disabled for a certain length of time (parameter A5)
from the start of the storage phase and after a defrost. This
alarm is not activated/managed if the cell probe is in alarm.
Effect: Storing of the alarm in the HACCP memory together
with the date and time.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "AL11 -
SOVRATEMPERATURA - OVER TEMPERATURE".
The symbol (14) flashes yellow.
Reset: Pressing the off beeper alarm silencer button or
switching off and switching on the card again (stand-by).

16.10 Black-Out Alarm

Cause: it is activated when a cycle in progress is interrupted
by a blackout, and when the duration of the blackout is
greater than the time defined by the parameter "uL".
Effect: Storing of the alarm in the HACCP memory together
with the date and time. The machine restarts the cycle set,
18
in the case of chilling time from the total time.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "AL12-
BLACKOUT DURATA 00 h 00' - DURATION BLACKOUT
00h00' '". The symbol (14) lights up flashing YELLOW (21)
Reset: Press the alarm silencer beeper off button
16.11 Compressor preventative maintenance
alarm
Cause: When the operating hours of the compressor are
an integer multiple of the hours set (if alarm activated).
Effect: none
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Display/LED: The display shows the scrolling text "SERVICE
+ TEL . 00000000000000 "(see parameter TEL)
Alternating with the time and temperature values repre-
sented. The symbol (14) flashes yellow.
Reset: Press the alarm silencer beeper off button
16.12 Temperature not reached in the time set
alarm
Cause: When temperature chilling lasts longer than the
times for Time out (parameter c1 or c4).
Effect:
signalling with flashing time or temperature dis-
play and beeper sound; press the "-" button (7) to stop the
signals.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) until the silencer button is pressed.
Reset: Press the alarm silencer beeper off button

16.13 Power keypad-card connection alarm

Cause: When there is no connection between the interface
and the power card
Effect: All the buttons are disabled. All the relays are de-
activated. All the inputs are ignored. The LED comes on
corresponding to the button that was pressed.
Beeper: The beeper sounds (3 seconds and then pauses
for 30 seconds) indefinitely.
Display/LED: The display (with scrolling text "AL15 - CON-
NESSIONE TASTIERA - KEYBOARD CONNECTION".
71503136-0-R000