Protección de distancia

Publicidad

Capítulo 5. Reenganchador
5.1.17 Nodos lógicos IEC 61850
Data Object
Common Data Class
Name
LNName
Data Objects
OpCntRs
INC
Controls
BlkRec1
SPC
BlkRec2
SPC
Status information
Auto
SPS
Op
ACT
Extended Data
SeqCrdIn
EXT_SPS
BlkRecStr
EXT_SPC
RecStr
EXT_ACT
IntnBlkCOF
EXT_SPS
IntnBlkDTr
EXT_SPS
IntnBlkCls
EXT_SPS
IntnBlkBF
EXT_SPS
IntnBlkOpn
EXT_SPS
IntnBlkSyn
EXT_SPS
IntnBlkTr
EXT_SPS
RecBlkCmd
EXT_SPS
AutoRecSt
EXT_ENS
IntnBlk
EXT_SPS
RecGTmIn
EXT_SPS
RsBlkRec1
EXT_SPC
RsBlkRec2
EXT_SPC
RecTmSt1
EXT_SPS
RecGnTmSt1
EXT_SPS
RecPhTmSt1
EXT_SPS
ManClsTmSt
EXT_SPS
RecTmSt2
EXT_SPS
RecPhTmSt2
EXT_SPS
RecGnTmSt2
EXT_SPS
RecTmSt3
EXT_SPS
RecPhTmS3
EXT_SPS
RecGnTmSt3
EXT_SPS
RecTmS4
EXT_SPS
RecPhTmSt4
EXT_SPS
RecGnTmSt4
EXT_SPS
ExClsTmSt1
EXT_SPS
ExClsTmSt2
EXT_SPS
CLASS IRLRREC
Explanation
The name shall be composed of the class name, the LN-Prefix
and LN-Instance-ID according to IEC 61850-7-2, Clause 22
Resettable Operation Counter
External block
Manual block
Automatic operation
Operate
Sequence coordination activation input
Recloser start block input
Recloser start
Internal block due to COF
Internal block due to definitive trip
Internal block due to closing failure
Internal block due to failure at the beginning
Internal block due to breaker in open status
Internal block due to lack of synchrocheck
Internal block due to three phase trip
Internal block due to command
Recloser in progress
Block by any reason
Ground faults reclose time input
External unblock command
Manual unblock command
Recloser in three phase cycle time 1
Recloser in three phase cycle time 1 with ground fault
Recloser in three phase cycle time 1 with phase fault
Recloser in manual close time
Recloser in cycle time 2
Recloser in cycle time 2 with phase fault
Recloser in cycle time 2 with ground fault
Recloser in cycle time 3
Recloser in cycle time 3 with phase fault
Recloser in cycle time 3 with ground fault
Recloser in cycle time 4
Recloser in cycle time 4 with phase fault
Recloser in cycle time 4 with ground fault
Recloser in security time after manual closing
Recloser in security time after manual closing through recloser
 ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2018
M0ZLFA1807E
5.1-28
ZLF: Protección de Distancia