PIXIT for Control model
ID
Ed
Description
Ct1
1
What control models are supported
(compare ICD file enums for Ed2)
Ct2
1,2
Is the control model fixed, configurable and/or
dynamic
Ct3
-
Is TimeActivatedOperate supported (compare
PICS or SCL)
Ct4
-
Is "operate-many" supported (compare
sboClass)
Ct5
1
Will the DUT activate the control output when
the test attribute is set in the SelectWithValue
and/or Operate request (when N test
procedure Ctl2 is applicable)
Ct6
-
What are the conditions for the time (T)
attribute in the SelectWithValue and/or
Operate request
Ct7
-
Is pulse configuration supported (compare
pulseConfig)
Ct8
1
What is the behaviour of the DUT when the
check conditions are set
Is this behaviour fixed, configurable, online
changeable
Value / Clarification
DOns: Y
SBOns: Y
DOes: Y
SBOes: Y
Dynamic
Deprecated
Deprecated, see sboClass in
datamodel (ICD)
N
Deprecated
Deprecated
N synchrocheck
Y interlock-check
DUT ignores synchrocheck value.
DUT uses interlock-check to perform
or not the check.
Fixed
11