ID
Ed
Description
Rp12
2
After restart of the server is the value of ConfRev
restored from the original configuration or
retained prior to restart
Rp13
1,2
Does the server accepts any client to
configure/enable a BRCB with ResvTms=-1?
What fields are used to do the identification?
Rp14
2
When BRCB.ResvTms is exposed, what is default
value for BRCB.ResvTms if client does not write
(must be > 0)
or
When BRCB.ResvTms is not exposed, what is the
internal reservation time (must be >= 0)
<additional items>
PIXIT for Logging model
ID
Ed
Description
Lg1
1,2
What is the default value of LogEna
(Compare IEC 61850-8-1 $17.3.3.2.1, the default
value should be FALSE)
Lg2
-
What is the format of EntryID
Lg3
1,2
Are there are multiple Log Control Blocks that
specify the Journaling of the same MMS
NamedVariable and TrgOps and the Event
Condition
(Compare IEC 61850-8-1 $17.3.3.3.2)
Lg4
1
Pre-configured LCB attributes that cannot be
changed online
<additional items>
Value / Clarification
Restored from original CID
configuration
N
Client's IP Address
10 seconds
N/A
Value / Clarification
FALSE
Deprecated
Single Journal Entry
LogRef and DatSet (DatSet is
configurable by the IED tool)
7