ZIV ZLF Serie Manual De Instrucciones página 600

Protección de distancia

Publicidad

Capítulo 6. Supervisión y Control
6.12.5 Nodo lógico IEC 61850
Data Object
Common Data Class
Name
LNName
Data Objects
Measured values
SumSwARs1
BCR
SumSwARs2
BCR
SumSwARs3
BCR
OpCntRs1
INC
OpCntRs2
INC
OpCntRs3
INC
OpCntRs4
INC
SwA1
MV
SwA2
MV
SwA3
MV
Status information
ArcStrIn1
SPS
ArcStrIn2
SPS
ArcStrIn3
SPS
NumTrAlm
SPS
SwAAlm1
SPS
SwAAlm2
SPS
SwAAlm3
SPS
SwARsCmd1
SPC
SwARsCmd2
SPC
SwARsCmd3
SPC
SwABlkIn
SPS
OpCntRs1
INC
OpCntRs2
INC
OpCntRs3
INC
CBInA
SPS
CBInB
SPS
CBInC
SPS
CBInOR
SPS
CBInAND
SPS
AnyPoleOpn
ACT
OnePoleOpn
SPS
AllPoleOpn
SPS
OpnFail
SPS
ClsFail
SPS
ColOpn
SPS
ColCls
SPS
CLASS ZLFSCBR
Explanation
The name shall be composed of the class name, the LN-Prefix
and LN-Instance-ID according to IEC 61850-7-2, Clause 22
Accumulative KA2 phase A
Accumulative KA2 phase B
Accumulative KA2 phase C
Number of pole A closing operations
Number of pole B closing operations
Number of pole C closing operations
Number of pole 3 phase closing operations
Current opened phase A
Current opened phase B
Current opened phase C
Pole A arc initiation input
Pole B arc initiation input
Pole C arc initiation input
Alarm excessive number of trips
Alarm KA2 phase A
Alarm KA2 phase B
Alarm KA2 phase C
Reposition command KA2 phase A
Reposition command KA2 phase B
Reposition command KA2 phase C
Accumulative kA2 block input
Reposition command open current phase A
Reposition command open current phase B
Reposition command open current phase C
Breaker pole A open input
Breaker pole B open input
Breaker pole C open input
Breaker any pole open input
Breaker all pole open input
Breaker any pole open
Breaker one pole open
Breaker all pole open
Breaker open command failure
Breaker close command failure
Breaker open command executed
Breaker close command executed
 ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2018
M0ZLFA1807E
6.12-6
ZLF: Protección de Distancia