Tables 1 – Installation data for FC5AZQ units
Evaporator
Suction line
diameter
Liquid line
diameter (up to 30m)
Maximum piping length
Maximum unlevel between the
units
Refrigerant charge
Condenser + Evaporator
Addition of oil
Evaporator
Suction line
diameter
Liquid line
diameter (up to 30m)
Maximum piping length
Maximum unlevel between the
units
Refrigerant charge
Condenser + Evaporator
Addition of oil
FC5 units, 057 to 180, have a condensate draining
outlet on the left side. Install the condensate draining
line with proper siphons.
The set of items for the drain connection shall be
acquired in separate for field installation. This line,
which shall not have a diameter smaller than 3/4", must
have immediately after the unit outlet, a siphon to
ensure the air tightness, and the condensate draining
when the unit is operating. At the initial start-up, this
siphon must be filled with water in order to prevent
the air from being suctioned from the draining line.
The siphon must be dimensioned according to the
pressure foreseen for the collecting tray (pay attention
to installations with ducted return).
Check if the location is free from dust and other
suspended particles that cannot be caught by the air
filters, and may obstruct the air coils.
Aiming at a perfect draining of the condensate formed
during the operation, install the equipment a little
tilted towards the side of the draining lines outlet (5
to 10mm).
M A N U A L D E I N S TA L A C I Ó N , O P E R A C I Ó N Y M A N T E N I M I E N T O
FC5AZQ036
FC5AZQ057
3/4" (up to 10m)
7/8" (up to 20m)
7/8" (10 to 30m)
1.1/8" (20 to 30m)
3/8"
The refrigerant charge shall comply with the procedures and the overheating and subcooling limits
FC5AZQ120
FC5AZQ160
1.1/4" (up to 20m)
1.1/8" (up to 20m)
1.3/8" (20 to 30m)
1.3/8" (20 to 30m)
1/2"
30m (equivalent length per circuit)
Inside unit below the outside one: 19,8m
Inside unit above the outside one: 22,9m
The refrigerant charge shall comply with the procedures and the
overheating and subcooling limits indicated in item 10 of this manual.
No extra oil is required up to 30m
FC5AZQ072
1.1/8" (up to 20m)
1.3/8" (20 to 30m)
1/2"
1/2"
30m (equivalent length per circuit)
12m
indicated in item 10 of this manual.
No extra oil is required up to 30m
FC5AZQ180
1.1/8" (up to 20m)
1.3/8" (20 to 30m)
5/8"
5/8"
Drain Connections
WRONG
RIGHT
Picture 5 - Drain Connections
FC5AZQ090
1.1/8" (up to 20m)
1.3/8" (20 to 30m)
1/2" (up to 20m)
3/4" (20 a 30m)
4.7
39