Connecting The Plant Components - Heyl Testomat 2000 Instrucciones De Operación

Ocultar thumbs Ver también para Testomat 2000:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Connection example
Limit value contact LV 1
switches mains voltage
n
3
4
5
e.g.
solenoid
valve
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Maintenan
18
19

Connecting the plant components

Connect the plant components to the output terminals of relays 1
to 19 (e.g. valves).
If the plant components require mains voltage, connect the
l
PE
switched mains voltage (l) to the common contact
respective relay (see the connection example for 230 VAC on the
left).
Connect the neutral conductor of the plant component to one of the
terminals (n).
For components with a protective earth conductor connection,
connect it to the PE connection.
Ensure that the leads are held securely in the terminals.
(Drawn relay positions: Instrument de-energized)
Type Function
Terminal
Flush
OUT External flush valve
Limit value output 1 – N/C
Limit value output 1 – N/O
LV1
OUT
Limit value output 1 - Common
Limit value output 2 – N/C
Limit value output 2 – N/O
LV2
OUT
Limit value output 2 - Common
Measuring point 1 – N/C
M. point.
Measuring point 2 – N/O
OUT
1/2
M. point switch-over - Common
AUX
OUT Universal output
Fault message output – N/C
Fault message output – N/O
Alarm
OUT
Fault message output - Common
Maintenance message – N/C
Maintenance message – N/O
OUT
ce
Maintenance message - Common
Installation
of the
Comment
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max,
max. 240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240VAC, 4A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A