Relay Output Connection; Solid-State Switch; Diode Protection - Siemens POINTEK CLS200 Manual De Arranque Rápido

Ocultar thumbs Ver también para POINTEK CLS200:
Tabla de contenido

Publicidad

Relay Output Connection

3
2
1
K2
NC
NO
COM
Switch and potentiometer settings are for illustration purposes only.
Note:

Solid-state Switch

K3
1
2

Diode Protection

When driving an external relay with either the solid-state switch and/or relay outputs
using DC power, protection diodes must be connected in the correct polarity across the
relay coil to prevent possible switch/relay damage resulting from inductive spikes
generated by the relay coil.
Page 24
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
The relay is shown in a de-energized/unpowered state.
K2 contact ratings:
max. switching voltage/current (DC): 30 V DC / 5 A
max. switching voltage/current (AC): 250 V AC / 8 A
max. switching capacity: 150 W / 2000 VA
Solid-state switch to customer's control or instrumentation device.
The switch is shown in de-energized/unpowered state.
K3 contact ratings:
Maximum Voltage: 30 V DC or peak AC
Maximum Current: 82 mA
Non-polarized
relay coil
customer-supplied
diode protection
relay coil
customer-supplied
diode protection
7ML19985JH04

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pointek cls300

Tabla de contenido