Mounting Restrictions - Siemens POINTEK CLS200 Manual De Arranque Rápido

Ocultar thumbs Ver también para POINTEK CLS200:
Tabla de contenido

Publicidad

Angled mounting
Pointek CLS300 cable version:
The cable version is designed for top mounting. The cable suspends vertically so that it
reaches into the process at the desired detection level (high or low detection alarm).

Mounting Restrictions

Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 500 mm (20") between them, to prevent
interference.
Side View
(section)
500 mm
(20") min
500 mm
(20") min
Sensors must be 500 mm (20") apart.
Page 18
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
Angle
Multiple Units
End View
500 mm
(20") min
Mount diagonally if space is restricted.
7ML19985JH04

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pointek cls300

Tabla de contenido