Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent
interference.
In nozzle
Side View
100 mm
(4") min
100 mm
(4") min
Sensors must be at least 100 mm (4") apart.
Page 14
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
50 mm (2")
minimum
> 100mm
Multiple Units
Close to tank walls
(4") Ø
50 mm (2") min
End View
Mount diagonally if space is restricted
50 mm
(2")
min
100 mm
(4") min
7ML19985JH04