Set-up mode / run mode: S5
S5-ON Set-up mode
S5-OFF Run mode
Test settings: S4
When S4 is set to ON, it inverts the signal, allowing you to test the delay settings
from P1, or to verify that S1 and S2 are in the correct position.
S4-ON
Enable test
S4-OFF Normal operation

Setup

WARNING: It is essential to check settings during the process itself,
and confirm that they are correct, before regular operation
commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
7ML19985JH04 Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
Use this setting only during trip-point set-up.
Use this setting during normal operation after set-up is
complete.
Observe the response of the output status and sensor
status LEDs to verify the delay interval set by
potentiometer P1.