Sensitivity setting (high or low): S5
S5-ON
High sensitivity
S5-OFF Low sensitivity
Test settings: S4
When S4 is set to ON, it inverts the signal, allowing you to test the delay settings
from P1, or to verify that S1 and S2 are in the correct position.
S4-ON
Enable test
S4-OFF Normal operation

Setup

WARNING: It is essential to check settings during the process itself,
and confirm that they are correct, before regular operation
commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
For a simple application, set Pointek CLS300 to Low alarm/no delays:
turn P1 fully counter-clockwise (no delay interval)
set dip switches S1, S2 and S5 to ON, S3 and S4 to OFF
S1-ON Delay disabled
S2-ON Delay disabled
S3-OFF Low alarm
S4-OFF Test function disabled
S5-ON High sensitivity
7ML19985JH04 Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
Use this setting for measuring dry solids or non-
conductive liquids.
Use this setting for measuring conductive liquids, or
viscous conductive solids that can build up on the sensor.
Observe the response of the output status and sensor
status LEDs to verify the delay interval set by
potentiometer P1.
• probe uncovered = alarm ON/relay de-
energized
• normal operation
• default setting
• for dry solids or non-conductive liquids