Location

Recommended:
Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
Avoid mounting Pointek CLS200 in locations subject to strong vibrations in the
vicinity, whenever possible.
Do not exceed the permissible ambient temperature limits (see
page 9 for details).

Mounting

Pointek CLS200 (compact threaded probe shown )
High level alarm
vertical
normal process
level
For high level alarm (level exceeds normal process level):
normally mounted into the vessel top, or
mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
mounted through the tank wall at the detection level
Pointek CLS200 typical configuration with extensions:
For high or low level alarm:
designed for top mounting. The probe suspends vertically so that it reaches into
the process at the desired detection level (high or low detection alarm).
High level alarm
7ML19985JH04
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
normal process
level
Angle
Environmental
Low level alarm
horizontal
Low level alarm
on
normal process
level
normal process
level
Page 13