Ride Profile And Sequence Setup; Up And Down Commands And Speed Reference Selection; Speed Selection Sequence Using Digital Inputs - Omron VARISPEED L7 Guia De Inicio Rapido

Ocultar thumbs Ver también para VARISPEED L7:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 66

Ride Profile and Sequence Setup

Up and Down Commands and Speed Reference Selection

Up/Down Command Source Selection
The input source for the Up and Down signal can be selected in parameter b1-02. The factory setting is Up/
Down command by the terminals S1/S2 (b1-02 = 1).
Travel start in Up or Down direction
To start in the elevator in Up or Down direction the following conditions have to be fulfilled:
At least one speed reference must be selected if digital inputs are used for speed reference selection.
The hardware base block signal (Terminal BB and BB1) must be set (not base block condition).
The Up/Down signal must be set to start in the corresponding direction.
Travel stop
The inverter can be stopped as follows:
The direction command (UP or Down) signal is removed.
The speed reference selection signal is removed if digital inputs are used for speed reference selection.
If d1-18 is set to 3 and all speed inputs are removed
Speed Reference Source Selection
The speed reference source can be selected using parameter b1-01. The factory setting is the digital operator
(b1-01 = 0), i.e. the speeds can be selected using digital inputs.

Speed Selection Sequence Using Digital Inputs

If the digital inputs are used for speed selection, the speed selection method and the speed priority depends on
the setting of parameter d1-18 (Speed priority selection).
Multi-Step Speed Operation 1/2 (Binary Input) (d1-18=0/3)
If d1-18 = 0
8 preset speed steps (defined in the parameters d1-01 to d1-08) can be selected using 3 binary coded digital
inputs. The Up/Down command starts the inverter. It stops when the Up/Down command is removed.
If d1-18 = 3
7 preset speed steps (defined in the parameters d1-02 to d1-08) can be selected using 3 binary coded digital
inputs. The Up/Down command starts the inverter. It is stopped when the Up/Down command is removed or
when no speed is selected (all D/Is off).
Multi-function Digital Input Settings (H1-01 to H1-05) (Example)
Terminal
S4
S5
S6
EN-19
All manuals and user guides at all-guides.com
Parameter
Set Value
Number
H1-02
3
Multi-step speed command 1
H1-03
4
Multi-step speed command 2
H1-04
5
Multi-step speed command 3
Details

Publicidad

Tabla de contenido
loading

Tabla de contenido