5 Installation
The activities described in this section must only
be executed by a qualified electrician.
T
ATTENTION
Damage to the device by improper handling
Collisions and shocks may damage the device.
f Avoid collisions and impacts.
f Use a soft base to set down the device.
f Do not use the bolts for fastening the front panel as a
transport aid or handle.
5.1
Choice of location
The unit is intended for permanent installation and for
indoor and outdoor use. A suitable location meets the fol-
lowing requirements:
Technical data and mains data are the same.
Î "4 Technical data"
Permissible ambient conditions are observed.
Î "5.2 Permitted environmental conditions"
The following minimum distances to other objects (e. g.
walls) must be complied with:
Distance to the left and right: 300 mm
Distance upward: 300 mm
Operating mode "Backend-System": The mobile net-
work for connection to the Backend-System must be
fully available at the location.
"Networked" operating mode: Networked devices are
in sufficient proximity to each other (The Ethernet cable
may not exceed 100 m in length).
The device and the charging station are in sufficient
proximity to each other, depending on the charging
cable used.
12
5.2 Permitted environmental conditions
T
DANGER
Danger of injury and fire
If the device is operated in potentially explosive atmos-
pheres (explosive area), explosive substances may ignite
due to sparking of components of the device.
f Do not use charging cable in potentially-explosive
atmospheres (e.g. at gas filling stations)
T
ATTENTION
Device damage due to unsuitable ambient conditions
Unsuitable ambient conditions can result in device dama-
ge.
f Avoid direct sunlight.
f Protect the device from a direct water jet.
f Ensure adequate ventilation of the device.
Do not install in niches.
f Keep device away from heat sources.
f Avoid strong temperature fluctuations.
Permitted environmental conditions
Ambient temperature
Average temperature
over 24 hours
Altitude
Relative humidity
-25 ... +40 °C
< 35 °C
Max. 2,000 m above sea
level
max. 95% (non-condensing)