9 Settings
Name
Description
Domestic hot water temperature setpoint.
In the case of operation with a calorifier tank and pro­
DP070
gramming via room unit corresponding to the comfort
setpoint [°C]
* Depends on the market
Enabling the calorifier tank sensor/thermostat
DP150
0: DHW (Domestic Hot Water) sensor
1: DHW (Domestic Hot Water) thermostat
Temperature setpoint of the anti-legionella function
DP160
[°C]
DHW mode:
0: Domestic hot water programming (only available
with Room Unit)
DP200
1: Manual (boiler with calorifier tank) – Preheating ac­
tive (instantaneous boiler) **
2: Antifreeze (boiler with calorifier tank) – No preheat­
ing (instantaneous boiler)*
Duration of the DHW anti-legionella program [mi­
DP410
nutes]
DP420
Maximum anti-legionella duration time [minutes]
Day to start the DHW anti-legionella program [day]
1: Monday
2: Tuesday
3: Wednesday
DP430
4: Thursday
5: Friday
6: Saturday
7: Sunday
Starting time for the DHW anti-legionella program [mi­
DP440
nutes]
GP007
Maximum fan speed in heating mode [rpm]
GP008
Minimum fan speed [rpm]
GP009
Fan starting speed [rpm]
Enabling domestic water circuit during chimney
GP082
sweep function
Pump post circulation run time after heating mode re­
PP015
quest [min]
PP016
Maximum pump speed in heating mode [%]
PP018
Minimum pump speed in heating mode [%]
DEAIR
Manual degassing function
CNF
Configuration CN1 and CN2
AD
Searching for devices connected to the boiler PCB
Tab.116 Settings table with SMART TC°
Name
Description
Required ambient temperature (°C) in the zone in
CP060
the holiday/antifreeze period
Maximum ambient setpoint temperature (°C) in re­
CP070
duced mode that enables switching to comfort
mode with climate control (with outside sensor)
190
INIDENS
Factory
Minimum
value
(55/60) *
35
1
65
60
2 (*) / 1 (**)
3
0
15
0
1
1
30
0
See chapter
"Service Set­
tings"
See chapter
"Service Set­
tings"
4300
( 24/28 MI)
2500
4800
( 30/35 MI)
0
0
3
0
100
85
85
85
- - -
- - -
Factory
Minimum
value
6
5
17
5
Maximum Level
(60/65) *
User
Installer
90
Installer
User
600
Installer
360
Installer
7
Installer
143
Installer
Installer
Installer
6000
Installer
1
Installer
99
Installer
100
Installer
100
Installer
Installer
Installer
Installer
Maximum
Level
20
User
30
User
7804841 - 02 - 20012022