10 Maintenance
10.3.8

Electrode distances

Fig.135
Electrode distance
4.0 ± 0.7
Verify the distances between the electrode and the burner and between the ignition electrode and the flame detection electrode.
10.3.9

Water unit

Caution
Do not use tools to remove components from inside the water unit (e.g. filter).
For certain user areas, where water hardness values exceed 15 °F (1 °F = 10 mg of calcium carbonate per litre of water) it is
recommended to install a polyphosphate batcher or equivalent system that complies with the prevailing standards.
CLEANING THE FILTERS
The domestic water filter is housed inside a removable cartridge. The domestic water circuit is positioned on the cold water inlet.
Proceed as follows to clean the filter:
1. Disconnect the power supply to the boiler;
2. Close the domestic water inlet cock;
3. Remove the filter by loosening the cartridge (B);
4. Remove any impurities and deposits from the filter;
5. Fit the filter back inside the cartridge and reinsert it into its seat, securing it with a suitable spanner.
200
INIDENS
Caution
The maximum tightening torque of the four M6 nuts (D) fastening
the flange is 5 Nm ( +/- 0.5).
BO-7726650-1