Descargar Imprimir esta página

Electrical Connection - Hoshizaki KM-590DJE-R452 Manual De Instrucciones

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 64
ENGLISH
F. Electrical Connection
For All Models
1. Hard-wired electrical connection is recommended.
Electrical connection must meet national, state,
and local electrical code requirements. Failure to
meet these code requirements could result in death,
electric shock, serious injury, fire, or severe damage
to equipment.
2. This unit requires an independent power supply of
proper capacity. See the nameplate for electrical
specifications. Failure to use a properly sized
breaker or fuse can result in a tripped breaker, blown
fuses, or damage to existing wiring. This could lead
to heat generation or fire.
3. THIS UNIT MUST BE GROUNDED (EARTHED).
Failure to properly ground (earth) this unit could
result in death or serious injury.
• Usually an electrical permit and services of a licensed
electrician are required.
• The maximum allowable voltage variation is
±10 percent of the nameplate rating.
• The neutral terminal on the terminal block (light blue
wire) must be connected to the neutral conductor of the
power source. See Fig. 7. CAUTION! Miswiring may
result in severe damage to the icemaker.
GR/Y
BR
LBu
Junction Box
Terminal Block
Wire Color Code:
GR/Y–green-and-yellow
BR–brown
LBu–light blue
WARNING
7/8" (22.2 mm)
Diameter Opening
Fig. 7
• The opening for the power supply connection is
7/8" (22.2mm) DIA to fit a 1/2" trade size conduit.
• If a power cord is used to provide electricity to the
icemaker in place of a hard-wired (conduit) connection,
a strain relief (gland) of the appropriate size for the
power cord must be installed at the 7/8" (22.2 mm)
diameter opening for the power supply connection.
WARNING! The power cord and its conductors must
be appropriately sized and rated for the electrical
consumption of this icemaker. See the nameplate for
electrical specifications.
For the UK and the Republic of Ireland Only
For installations to pre-IEC 60446 field wiring, the colors
of the wires in the icemaker's junction box may not
correspond with the colors of the field wiring. In this case,
proceed as follows:
The icemaker terminal with the green-and-yellow wire
must be connected to the incoming green or green-and-
yellow wire which connects to the terminal marked with
the letter "E", the symbol
and-yellow. The icemaker terminal with the light blue
wire must be connected to the incoming black wire which
connects to the terminal marked with the letter "N" or
the color black. The icemaker terminal with the brown
wire must be connected to the incoming red wire which
connects to the terminal marked with the letter "L" or the
color red.
9
, or the color green or green-

Publicidad

loading