Room Controller
Specifications
Electrical Ratings
Input Voltage
Relay Rating
General Use:
Standard Ballast:
Electronic Ballast:
Incandescent Load:
Motor Load:
Control Voltage
Controller Connections
Line Voltage
Room Controller
Operating Environment
Housing
BMS Output Click & Go Connection
The Room Controller provides a dry contact closure output to a BMS or other system to indicate that the room is occupied. The BMS
output will close when the occupancy sensor senses motion (even when in Vacancy Mode) or when any switch button is pressed to
turn lighting loads ON. The BMS output will open when the occupancy sensor no longer senses motion or, in applications where there
is no occupancy sensor, when commanded into After-Hours Mode from an external contact.
(Class 2)
BMS System
Press Here
Blue
Red
Closure to
BMS System
The Receptacle/BMS out port supports the use of a Receptacle Switchpack or BMS Output. Do not tie both items into the port at the
same time. Presence of the Receptacle Switchpack will cause 24 VDC to be present on the BMS output which may cause damage to
the connected system.
www.cooperlighting.com
120 VAC 50/60Hz
120, 240, 277 VAC 50/60Hz
20A
20A
16A
20A
1HP @ 120 VAC
24 VDC supplied by Receptacle
Switchpack
Flying leads
Click & Go port/QuickConnect
cable
32° F to 104° F (0° to 40° C)
For indoor use only.
Medium impact injection molded
plastic housing. ABS resin
complies with UL 94V0. Plenum
rated for external junction box
mounting, with Teflon coated
leads.
Connect the OCC-RJ45 Input/Output Device to the BMS system.
Closure will be made across the Blue and Red wire
OCC-RJ45
locations. Connect a QuickConnect cable between the
(Input/Output Device)
Receptacle/BMS Out Click & Go port on the Room
Controller and to one of the ports on the OCC-RJ45 ports.
Blue
Red
Black
Brown
Click & Go
Ports
QuickConnect Cable
(Class 2)
6
Switchpack
White
Red
Receptacle
BMS/Out
5
Black
Sensors
Green
Sensors
Slider
Station
4
Wallstations
-
A/V
Mode
+
-
3
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
2
1
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1 2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
CAUTION
Greengate
5
9850-000362-06 page 12
October 2022