Room Controller
Input
Time Clock functionality will change if an occupancy
sensor is connected to a Room Controller based on
occupied and unoccupied status
Switches the controller between After-Hours Mode
and Normal Mode.
Contact Type Required: Normally Open, SPST
Maintained.
Time clock input will vary if there is no occupancy
sensor connected to the Room Controller
Time Clock
Mode
Overrides system functions to allow for fire alarm,
emergency or other systems needing to call lighting
to a full ON condition.
Contact Type Required: Normally Open, SPST
Maintained.
Alert Mode
Dimmers reduce current level and maximum output
by 10%, 20%, 30% or 40% based on DIP Switch
Demand
setting.
Response
Mode
Contact Type Required: Normally Open, SPST
Maintained.
Allows a 3rd party device or system to activate and
de-activate the A/V scene.
A/V Mode
Contact Type Required: Normally Open, SPST
Momentary.
*Connected alternate voltage and receptacle switchpacks will not blink warn with onboard relay loads. They will remain ON
during the blink warn process and will turn OFF with other lighting once the warning periods expire.
www.cooperlighting.com
Function
Position
Occ Sensor Connected & Occupied:
DIP#3&#4 ON lighting = SCENE 6, Rec=ON
DIP#3ON, #4OFF lighting = ALL ON, Dim 50%, Rec=ON
DIP#3&#4 OFF lighting = Manual ON, Rec=ON
Occ Sensor Connected & UnOccupied:
Time Clock
Lighting = OFF
Open
Receptacle = OFF (30seconds after lighting)
No Occ Sensor Connected:
Lighting = Blink warn OFF (5min)
Manual ON button press has a 1hr timer
Receptacle = OFF (30 seconds after lighting)
Occ Sensor Connected & Occupied:
DIP#3&#4 ON lighting = SCENE 6, Rec=ON
DIP#3ON, #4OFF lighting = ALL ON, Dim 50%, Rec=ON
DIP#3&#4 OFF lighting = Manual ON, Rec=ON
Occ Sensor Connected & UnOccupied:
Time Clock
Closed
Lighting = Scene 5
Receptacle = ON
No Occ Sensor Connected:
Lighting = Scene 5
Receptacle = ON
Occ Sensor Connected & Occupied:
Lighting= No Change
Receptacle = ON
Occ Sensor Connected & UnOccupied:
Time Clock
Sweep
Lighting = OFF
(pulsed)
Receptactle = OFF (30 seconds after lighting)
No Occ Sensor Connected:
Lighting = Blink warn OFF (5min)
Receptact = OFF (30 seconds after lighting)
Onboard relays close. Dimmers go to full. Solatubes open.
Closed
Receptacle Switchpack turns OFF. Wallstation, occupancy
and daylight controls are disabled.
System is returned to normal function leaving lighting in
Open
current state. If no occupancy sensor closure is detected,
lighting will blink warn and turn OFF 5 minutes later.
Dimmers reduce by selected percentage over a 2 minute
Closed
period. Controller continues to operate lighting within the
reduced range.
Open
Lighting range will revert to full scale.
Toggles between A/V Mode and Normal Mode. In A/V
Mode, relays will stay in their previous configuration.
Momentary
Dimmers will be reduced to maintain light levels at 20%
Closure
by default or other light level if reprogrammed using the
Room Controller Personal Remote (HHPR-RC).
Greengate
Operation
9850-000362-06 page 14
October 2022